MAIN BURNER CHECK
Aerion Range
Inlet pressure test point
Access to HI fire regulator screw. If the pressure is more/less than the nominated pressure kPa adjust
the regulator. Access to regulator refer below. Remove the plastic plug covering the regulator
adjustment screw.
Insert the 2 mm wide flat bladed screwdriver and adjust the regulator
clockwise to increase and
counter-clockwise to decrease
the pressure. Note if the regulator had been over adjusted it may take a
few (10-12) rotations for the desired pressure to register.
Replace the plastic plug in reverse order.
With the full fire burner set turn the heater down to the low fire setting. If the pressure is more/less than
the pressure kPa highlighted on page 10-14 (dependant on model) of this manual adjust the regulator.
Access to regulator refer below. The regulator adjustment for low fire is located below the pressure
test points identified by the red paint. Insert the 4 mm Allen key and adjust the
regulator counter
clockwise to increase the pressure and clockwise to decrease
the pressure. Note this is opposite in
rotation to the high fire adjustment. The regulator injector is factory set and is fully (clockwise) closed.
When the pressure register’s
thew pressure as nominated pages 10-14 turn to high fire and check the
high fire has not deviated from burner pressure on High as nominated pages 10-14. Disconnect the
manometer from the inlet pressure point and tighten the screw
After checking the pressures and removing the manometers, the screws in the Pressure Test points
must be closed, and the system must be checked for gas-tightness.
Summary of Contents for Aerion Series
Page 7: ...PRODUCT DIMENSIONS 2 G1410 GF G1410 GF2L Aerion Range...
Page 8: ...PRODUCT DIMENSIONS 3 G1410 GF2R GF1410 GF3 Aerion Range...
Page 9: ...PRODUCT DIMENSIONS 4 G1410 RD G1410 T Aerion Range...
Page 10: ...PRODUCT DIMENSIONS 5 G1250 GF GF1250 GF2L Aerion Range...
Page 12: ...PRODUCT DIMENSIONS 7 G800 GF G800 T Aerion Range...
Page 13: ...PRODUCT DIMENSIONS 8 G650 Aerion Range ALTO GF...
Page 14: ...PRODUCT DIMENSIONS 9 ALTO T Aerion Range...
Page 22: ...17 Aerion Range UNIT TO TV CLEARANCES COMBUSTIBLE MANTLE Figure 1 4 Clearance from Unit to TV...
Page 104: ...Distributed By LIVING FIRE 61 3 99 777 888 info livingfire com au www livingfire com au...