8. SELECTING THE INSTALLATION SITE
Indoor Unit
AVOID:
Areas where leakage of flammable gas may be expected.
Places where large amounts of oil mist exist.
Direct sunlight.
Locations near heat sources which may affect the performance of the unit.
Locations where external air may enter the room directly. This may cause “condensation” on the air discharge
ports, causing them to spray or drip water.
Locations where the remote controller will be splashed with water or affected by dampness or humidity.
Installing the remote controller behind curtains or furniture.
Locations where high-frequency emissions are generated.
Places where blocks air passages.
Places where the false ceiling is not noticeably on an incline.
DO:
Select an appropriate position from which every corner of the room can be uniformly cooled.
Select a location where the ceiling is strong enough to support the weight of the unit.
Select a location where tubing and drain pipe have the shortest run to the outdoor unit.
Allow room for operation and maintenance as well as unrestricted airflow around the unit.
Install the unit within the maximum elevation difference above or below the outdoor unit and within a total tubing
length (L) from the outdoor unit as detailed in Table 1-1.
Allow room for mounting the remote controller about 1m off the floor, in an area that is not in direct sunlight or in
the flow of cool air from the indoor unit.
Places where optimum air distribution can be ensured.
Places where sufficient clearance for maintenance and service can be ensured.
When moving the unit during or after unpacking, make sure to lift it by holding its lifting lugs. Do not
exert any pressure on other parts, especially the refrigerant piping, drain piping and flange parts.
If you think the humidity inside the ceiling might exceed 30°C and RH 80%, reinforce the insulation on
the unit body. Use glass wool or polyethylene foam as insulation so that it is no thicker than 10 mm and
fits inside the ceiling opening.
CAUTION
Indoor Unit
Sec1.indd 55
2014/11/07 10:28:04
Summary of Contents for S-200PE1E8
Page 88: ...1 82 MEMO ...
Page 112: ...3 2 3 3 1 Outdoor Units Electric Wiring Diagram U 200PE1E8 U 250PE1E8 ...
Page 113: ...3 3 3 Schematic Diagram U 200PE1E8 U 250PE1E8 ...
Page 115: ...3 5 3 3 2 Indoor Units High Static Pressure Ducted Type S 200PE1E8A Electric Wiring Diagram ...
Page 116: ...3 6 3 3 2 Indoor Units High Static Pressure Ducted Type S 200PE1E8A Schematic Diagram ...
Page 117: ...3 7 3 3 2 Indoor Units High Static Pressure Ducted Type S 200PE1E8 Electric Wiring Diagram ...
Page 118: ...3 8 3 3 2 Indoor Units High Static Pressure Ducted Type S 200PE1E8 Schematic Diagram ...
Page 119: ...3 9 3 3 2 Indoor Units High Static Pressure Ducted Type S 250PE1E8 Electric Wiring Diagram ...
Page 120: ...3 10 3 3 2 Indoor Units High Static Pressure Ducted Type S 250PE1E8 Schematic Diagram ...
Page 129: ...4 9 4 4 3 Outdoor Unit Filter PCB FIL C906VH8 ...
Page 130: ...4 10 4 4 4 Outdoor Unit HIC Board HIC C906VH8 ...
Page 136: ... MEMO 4 16 ...
Page 154: ... MEMO 5 18 ...
Page 164: ... MEMO 6 10 ...
Page 180: ... MEMO 7 16 ...
Page 197: ...201411 ...