7
7
Item code
Item
Setting data
No.
Description
Fan tap setting
(Fan tap change in order
to prevent drop in air
discharge caused by filter
installation)
DC fan tap
operating mode
Purpose
0000
Standard
Standard (setting at shipment)
0001
High ceiling use High ceiling setting 1 (with standard panel)
For low static-
pressure filter
Ultra long-life filter, oil guard panel, ammonia
deodorizing filter, optical regenerative
deodorizing filter
0003
High ceiling use High ceiling setting 2 (with standard panel)
For low static-
pressure filter
(Antibacterial) high-performance filter (90%)
(Antibacterial) high-performance filter (65%)
Air-cleaning unit, air-cleaning unit + optical
regenerative deodorizing filter, deodorant
(activated charcoal) filter
For air-blocking
material
For 3-Way discharge, when discharge duct is
connected
0006
For air-blocking
material
For 2-Way discharge
Humidifier ON time
(ON time per 60 seconds)
0000
No humidifier output
0001
1 second.
0002
2 seconds.
0058
58 seconds.
0059
59 seconds.
0060
Continuously ON
Repeat timer switching
0000
Function disabled
0001
Function enabled
Timer function change
prohibit
0000
Function disabled
0001
Function enabled
Smudging control
0000
No smudging control
7-8
SM830194-04_Single_BigPAC.indb 8
2014/11/14 14:38:37
Summary of Contents for S-200PE1E8
Page 88: ...1 82 MEMO ...
Page 112: ...3 2 3 3 1 Outdoor Units Electric Wiring Diagram U 200PE1E8 U 250PE1E8 ...
Page 113: ...3 3 3 Schematic Diagram U 200PE1E8 U 250PE1E8 ...
Page 115: ...3 5 3 3 2 Indoor Units High Static Pressure Ducted Type S 200PE1E8A Electric Wiring Diagram ...
Page 116: ...3 6 3 3 2 Indoor Units High Static Pressure Ducted Type S 200PE1E8A Schematic Diagram ...
Page 117: ...3 7 3 3 2 Indoor Units High Static Pressure Ducted Type S 200PE1E8 Electric Wiring Diagram ...
Page 118: ...3 8 3 3 2 Indoor Units High Static Pressure Ducted Type S 200PE1E8 Schematic Diagram ...
Page 119: ...3 9 3 3 2 Indoor Units High Static Pressure Ducted Type S 250PE1E8 Electric Wiring Diagram ...
Page 120: ...3 10 3 3 2 Indoor Units High Static Pressure Ducted Type S 250PE1E8 Schematic Diagram ...
Page 129: ...4 9 4 4 3 Outdoor Unit Filter PCB FIL C906VH8 ...
Page 130: ...4 10 4 4 4 Outdoor Unit HIC Board HIC C906VH8 ...
Page 136: ... MEMO 4 16 ...
Page 154: ... MEMO 5 18 ...
Page 164: ... MEMO 6 10 ...
Page 180: ... MEMO 7 16 ...
Page 197: ...201411 ...