Sensor Temperature Display Function (Displayed regardless of operation and stop)
The below check procedure can be used to display all remote
controller, indoor unit, and outdoor unit sensor temperatures.
<Check procedure>
(1) Press and hold the
button and
button simultaneously for
4 seconds or longer.
(2) Unit No. X-X (main unit No.), item code XX (sensor address),
and service monitor 00XX (sensor temperature) appear on the
remote controller LCD. (See figure.)
(3) Press the temperature setting
and
buttons and
change the item code to the sensor address of the sensor that
you want to monitor.
(For the relationship between the sensor address and the
sensor type, refer to the below Sensor Temperature Correlation
Table.)
(4) During group control and simultaneous-operation multi control,
press the
button and change to the unit that you want to
monitor.
(5) Press the
button to return to normal remote controller
operation.
NOTE
The temperature display reads "- - - -" for units that are not connected.
* If monitor mode is selected during normal operation, the only parts of the LCD that change are those shown in
the figure 2.
All other displays do not change, and remain as they were during normal operation.
Sensor Temperature Correlation Table
Sensor installation
location
Sensor
address
Sensor type
Sensor
address
Sensor type
Indoor unit
00
Room temp.
(temp. used for control)*
05
–
01
Remote controller temp.
06
Discharge temp.
02
Indoor intake temp.
07
–
03
Indoor heat exchanger temp. (E1)
08
–
04
Indoor heat exchanger temp. (E2)
09
–
Outdoor unit
0A
Discharge temp. (TD)
12
–
0b
–
13
–
0C
Outdoor heat exchanger temp.
(C2)
14
Current
(AC current or CT 10 times
value)
0d
Intake temp. (TS)
15
Outdoor electronic control
valve position (PMV1)
0E
Outdoor heat exchanger temp.
(C1)
16
Outdoor electronic control
valve position (PMV2)
0F
–
17
–
10
–
18
–
11
Outdoor air temp.(TO)
19
Compressor frequency
* Main unit only when group control is enabled.
Example
1-1
: Unit No.
: Item code (sensor address)
: Discharge temp. (TD)
(3)
(2)
(5)
(1)
(4)
Fig.2
CZ-RTC2
SM830194-04_Single_BigPAC.indb 13
2014/11/13 18:18:56
Summary of Contents for S-200PE1E8
Page 88: ...1 82 MEMO ...
Page 112: ...3 2 3 3 1 Outdoor Units Electric Wiring Diagram U 200PE1E8 U 250PE1E8 ...
Page 113: ...3 3 3 Schematic Diagram U 200PE1E8 U 250PE1E8 ...
Page 115: ...3 5 3 3 2 Indoor Units High Static Pressure Ducted Type S 200PE1E8A Electric Wiring Diagram ...
Page 116: ...3 6 3 3 2 Indoor Units High Static Pressure Ducted Type S 200PE1E8A Schematic Diagram ...
Page 117: ...3 7 3 3 2 Indoor Units High Static Pressure Ducted Type S 200PE1E8 Electric Wiring Diagram ...
Page 118: ...3 8 3 3 2 Indoor Units High Static Pressure Ducted Type S 200PE1E8 Schematic Diagram ...
Page 119: ...3 9 3 3 2 Indoor Units High Static Pressure Ducted Type S 250PE1E8 Electric Wiring Diagram ...
Page 120: ...3 10 3 3 2 Indoor Units High Static Pressure Ducted Type S 250PE1E8 Schematic Diagram ...
Page 129: ...4 9 4 4 3 Outdoor Unit Filter PCB FIL C906VH8 ...
Page 130: ...4 10 4 4 4 Outdoor Unit HIC Board HIC C906VH8 ...
Page 136: ... MEMO 4 16 ...
Page 154: ... MEMO 5 18 ...
Page 164: ... MEMO 6 10 ...
Page 180: ... MEMO 7 16 ...
Page 197: ...201411 ...