1-49
1
1
Required space around outdoor unit
If the air discharge chamber is used, the space shown below must be secured around the outdoor unit.
If the unit is used without the required space, a protective device may activate, preventing the unit from operating.
(1) Single-unit installation
The top and both sides must remain open.
If there are obstacles to the front and rear of the outdoor unit,
the obstacle at either the front or rear must be no taller than the height of the outdoor
unit.
(2) Multiple-unit installation
Installation in lateral rows
The front and top must remain open.
The obstacles must be no taller than the height of the outdoor unit.
Installation in front-rear rows
Installation with intakes facing
intakes or outlets facing outlets
The front and both sides must remain open.
Reference diagram for air-discharge chamber (field supply)
The models of U-200PE1E8 / U-250PE1E8 with Air-Discharge Chamber
CAUTION
NOTE
The amount of space required for
removing the screws on the rear of
the unit.
If in case the sufficient space for
maintenance is ensured on the
rear of the outdoor unit, installation
is possible with the space of both
sides of not less than 150mm where
marked with * mark.
Unit: mm
Min.
500
or more
Min. 250* or
more
Not less than 150 or more
Unit: mm
Unit: mm
Min.
150
or more
Min. 250* or
more
Min.
200 or
more
Min. 1000 or more
Min. 300 or more
CAUTION
CAUTION
Sec1.indd 49
2014/11/07 10:28:02
Summary of Contents for S-200PE1E8
Page 88: ...1 82 MEMO ...
Page 112: ...3 2 3 3 1 Outdoor Units Electric Wiring Diagram U 200PE1E8 U 250PE1E8 ...
Page 113: ...3 3 3 Schematic Diagram U 200PE1E8 U 250PE1E8 ...
Page 115: ...3 5 3 3 2 Indoor Units High Static Pressure Ducted Type S 200PE1E8A Electric Wiring Diagram ...
Page 116: ...3 6 3 3 2 Indoor Units High Static Pressure Ducted Type S 200PE1E8A Schematic Diagram ...
Page 117: ...3 7 3 3 2 Indoor Units High Static Pressure Ducted Type S 200PE1E8 Electric Wiring Diagram ...
Page 118: ...3 8 3 3 2 Indoor Units High Static Pressure Ducted Type S 200PE1E8 Schematic Diagram ...
Page 119: ...3 9 3 3 2 Indoor Units High Static Pressure Ducted Type S 250PE1E8 Electric Wiring Diagram ...
Page 120: ...3 10 3 3 2 Indoor Units High Static Pressure Ducted Type S 250PE1E8 Schematic Diagram ...
Page 129: ...4 9 4 4 3 Outdoor Unit Filter PCB FIL C906VH8 ...
Page 130: ...4 10 4 4 4 Outdoor Unit HIC Board HIC C906VH8 ...
Page 136: ... MEMO 4 16 ...
Page 154: ... MEMO 5 18 ...
Page 164: ... MEMO 6 10 ...
Page 180: ... MEMO 7 16 ...
Page 197: ...201411 ...