2
2
2-17
NOTE
2-18. Items to Check Before the Test Run
(1)
(2)
Turn the remote power switch ON at least 12 hours in advance in order to energize the crank case heater.
Fully open the closed valves on the liquid-tube and gas-tube sides.
2-19. Test Run Using the Remote Controller
(1) Press and hold the remote controller
button for 4 seconds or longer. Then press the
button.
“TEST” appears in the LCD display during the test run.
Temperature control is not possible when test run mode is engaged.
(This mode places a large load on the devices. Use it only when performing the test run.)
(2) Use either Heating or Cooling mode to perform the test run.
The outdoor unit will not operate for approximately 3 minutes after the power is turned ON
or after it stops operating.
(3) If normal operation is not possible, a code appears on the remote controller LCD display.
Refer to “2-20. Table of Self-Diagnostic Functions and Corrections” and correct the problem.
(4) After the test run is completed, press the
button again.
Check that “TEST” disappears from the LCD display.
(This remote controller includes a function that cancels test run mode after a 60-minute timer has elapsed,
in order to prevent continuous test run operation.)
(5) For the test run of an inverter outdoor unit, operate the compressors for a minimum of 10 minutes
(in order to check for open phase).
* When performing a test run using a wired remote controller, operation is possible without attaching the
cassette-type ceiling panel. (“P09” will not be displayed.)
2-20. Table of Self-Diagnostic Functions and Corrections
Wired remote
controller
display
Indoor unit
receiver lamp
Cause
Correction
Group connection and simultaneous-operation multi
system
Nothing is
displayed
Nothing is
displayed.
• Remote controller is not connected with indoor unit
correctly.
• Indoor unit power is not ON.
Connect the remote controller correctly. Turn ON the
indoor unit power.
E01
displayed
Operation lamp
is blinking.
• Automatic address setting has not been completed.
• Inter-unit control wiring is cut or is not connected
correctly.
• Remote controller is not connected with indoor unit
correctly.
Check the remote controller and inter-unit control
wiring.
Perform automatic address setting (2-21).
E02
displayed
• Remote controller is not connected with indoor unit
correctly.
Connect the remote controller correctly.
E14
displayed
• Remote controller communication wiring is cut or is not
connected correctly.
Check the remote controller communication wiring.
Perform automatic address setting again.
E04
displayed
Standby lamp is
blinking.
• Indoor-outdoor inter-unit wiring is not connected
correctly.
Connect the wiring correctly.
E06
displayed
• Inter-unit control wiring is cut or is not connected
correctly.
Refer to 2-21-1. Basic wiring diagram, and make the
correct setting.
E15
Check that the total capacities of the indoor and
• Indoor unit capacity is too low.
outdoor units are appropriate.
E16
• Indoor unit capacity is too high.
P05
displayed
displayed
displayed
Operation lamp
and Standby
lamp are blinking
alternately.
• Reversed phase at one of the outdoor units in the group.
• Insufficient gas
Reverse 2 phases of the outdoor unit 3-phase power
and connect them correctly.
Fill up the gas appropriately.
P09
displayed
Timer lamp and
Standby lamp
are blinking
alternately.
• Ceiling panel connector at one of the indoor units in the
group is not connected correctly.
Connect the indoor unit ceiling panel connector
correctly.
P12
displayed
• DC fan trouble at one of the indoor units in the group.
Check whether the fan holder is loose.
Check the wiring between the DC fan and the PCB.
L02
L13
displayed
Both the
Operation lamp
and Standby
lamp are blinking
together.
Check that the indoor and outdoor unit types are
correct.
• Indoor-outdoor unit type mismatch.
L07
displayed
displayed
• Remote controller communication wiring is connected to
the indoor unit, however it is set for individual operation.
Perform automatic address setting (2-21).
L10
• Check outdoor operation with separate maintenance-use remote controller
.
SM830194-04_Single_BigPAC.indb 17
2014/11/04 13:45:15
Summary of Contents for S-200PE1E8
Page 88: ...1 82 MEMO ...
Page 112: ...3 2 3 3 1 Outdoor Units Electric Wiring Diagram U 200PE1E8 U 250PE1E8 ...
Page 113: ...3 3 3 Schematic Diagram U 200PE1E8 U 250PE1E8 ...
Page 115: ...3 5 3 3 2 Indoor Units High Static Pressure Ducted Type S 200PE1E8A Electric Wiring Diagram ...
Page 116: ...3 6 3 3 2 Indoor Units High Static Pressure Ducted Type S 200PE1E8A Schematic Diagram ...
Page 117: ...3 7 3 3 2 Indoor Units High Static Pressure Ducted Type S 200PE1E8 Electric Wiring Diagram ...
Page 118: ...3 8 3 3 2 Indoor Units High Static Pressure Ducted Type S 200PE1E8 Schematic Diagram ...
Page 119: ...3 9 3 3 2 Indoor Units High Static Pressure Ducted Type S 250PE1E8 Electric Wiring Diagram ...
Page 120: ...3 10 3 3 2 Indoor Units High Static Pressure Ducted Type S 250PE1E8 Schematic Diagram ...
Page 129: ...4 9 4 4 3 Outdoor Unit Filter PCB FIL C906VH8 ...
Page 130: ...4 10 4 4 4 Outdoor Unit HIC Board HIC C906VH8 ...
Page 136: ... MEMO 4 16 ...
Page 154: ... MEMO 5 18 ...
Page 164: ... MEMO 6 10 ...
Page 180: ... MEMO 7 16 ...
Page 197: ...201411 ...