7
7
Item code
Item
Setting data
No.
Description
Automatic drain pump
operation
0000
No forced operation
0001
Forced operation for 1 minute
0060
Continuous operation
Ventilation fan operation
0000
None
0001
Ventilation fan operated by remote controller.
Wired remote controller
sensor
0000
Not used. (Body sensor is used.)
0001
Remote control sensor is used.
“Operation change control in
progress” display
0000
Normal (displayed)
0001
Not displayed
OFF reminder function for
when weekly timer is used
0000
None
0001
Only stop time setting is enabled.
Heat exchanger temperature
for cold air discharge
(Heat exchanger control
point for control to prevent
cold air)
0013
Control temperature 13°C
0014
Control temperature 14°C
0025
Control temperature 25°C
0026
Control temperature 26°C
Fan output switching
0000
Output linked with fan. (ON when indoor unit fan is operating.)
0001
Fan mode operation output
Drain pump delayed start
time
0000
No delayed start
0001
1 sec. delayed start
Indoor
unit
Type E1
1 min. delayed start
Indoor
unit
Type E2
0002
2 sec. delayed start
2 min. delayed start
0058
58 sec. delayed start
58 min. delayed start
0059
59 sec. delayed start
59 min. delayed start
0060
60 sec. delayed start
60 min. delayed start
Humidifier setting
0000
Humidifier output OFF. Drain pump stopped.
0001
Humidifier output ON. Drain pump operates.
0002
Humidifier output ON. Drain pump operates for 1 minute when
total humidifier operating time reaches 60 minutes.
0003
Humidifier output ON. Drain pump stopped.
Flap operation mode
0000
Standard setting
0001
Draft reduction mode (Flap lower-limit position is shifted
upwards.)
Flap swing mode
0000
Smudging reduction mode (Flap swing upper-limit position is
shifted downwards.)
0001
Normal mode
0002
Draft reduction mode (Flap swing lower-limit position is shifted
upwards.)
7-7
SM830194-04_Single_BigPAC.indb 7
2014/11/14 14:38:36
Summary of Contents for S-200PE1E8
Page 88: ...1 82 MEMO ...
Page 112: ...3 2 3 3 1 Outdoor Units Electric Wiring Diagram U 200PE1E8 U 250PE1E8 ...
Page 113: ...3 3 3 Schematic Diagram U 200PE1E8 U 250PE1E8 ...
Page 115: ...3 5 3 3 2 Indoor Units High Static Pressure Ducted Type S 200PE1E8A Electric Wiring Diagram ...
Page 116: ...3 6 3 3 2 Indoor Units High Static Pressure Ducted Type S 200PE1E8A Schematic Diagram ...
Page 117: ...3 7 3 3 2 Indoor Units High Static Pressure Ducted Type S 200PE1E8 Electric Wiring Diagram ...
Page 118: ...3 8 3 3 2 Indoor Units High Static Pressure Ducted Type S 200PE1E8 Schematic Diagram ...
Page 119: ...3 9 3 3 2 Indoor Units High Static Pressure Ducted Type S 250PE1E8 Electric Wiring Diagram ...
Page 120: ...3 10 3 3 2 Indoor Units High Static Pressure Ducted Type S 250PE1E8 Schematic Diagram ...
Page 129: ...4 9 4 4 3 Outdoor Unit Filter PCB FIL C906VH8 ...
Page 130: ...4 10 4 4 4 Outdoor Unit HIC Board HIC C906VH8 ...
Page 136: ... MEMO 4 16 ...
Page 154: ... MEMO 5 18 ...
Page 164: ... MEMO 6 10 ...
Page 180: ... MEMO 7 16 ...
Page 197: ...201411 ...