9. The Self-Diagnosis Function Display and What is Detected
Alarm Display in the table below indicates the content of alarms that are displayed when a wired remote control is
connected. For information on how to deal with the alarms, refer to the Mounting Instructions for the indoor unit or
to Test Run or servicing materials.
WL Remote Control LED Display
Error Detected
Alarm Display
Run
Timer
Standby
Blinking
Communication error in the remote
control circuit
E01–E03, E08–E14, E17, E18
Communication error either in the in/
outdoor operation line or the sub-bus of
the outdoor unit
E04–E07, E15, E16, E19–E31
Operation of indoor protection device
P01, P09–P14
Alternately
Alternately
P02–P08, P15–P31
Operation of outdoor protection device
Error in the indoor thermistor
F01–F03, F10–F11
Alternately
Alternately
F04–F09, F12–F28
Error in the outdoor thermistor
Error in the indoor EEPROM
F29
Simultaneously
Error in the outdoor EEPROM
F30, F31
Simultaneously
Error related to the compressor
H01–H31
Error in indoor settings
L01–L03 L05–L09
Simultaneously
Error in outdoor settings
L04, L10–L31
Simultaneously
Inconsistency in Air/Heat (Including an auto-temp setting for a model
without auto-temp settings)
Alternately
Oil Alarm (Same as operation of outdoor protection device)
Alternately
Test Run
Simultaneously
: Off / : On /
: Blinking (0.5 sec. intervals)
When using CZ-RWSC2
If you have either an outdoor maintenance remote control or a wired
remote control and a service checker special wiring (CV6231785082 :
for service use) at hand, you can get more detailed information about
an alarm by connecting one to the service connecter as in the diagram.
For information such as how to connect to receivers, etc., refer to the
Users Manual that came attached with the service checker special
wiring.
10. Room Temperature Sensor Settings
•
The indoor unit and the wireless remote control are equipped with
indoor temperature sensors. The sensing of indoor temperature
works via one of them.
•
W
hen the unit is shipped, it is set to the indoor unit, but to switch to
the remote control, press the Sensor button (diagram at right) inside
the remote control’s cover and then check to make sure that Main
Sensor on the LCD screen goes off.
NOTE
Even when the Sensor switch has been set to the remote control,
if the unit does not receive any room temperature data from the remote
control for ten minutes, it automatically switches back to the indoor unit
sensor, so be sure to install the remote control facing the receiver.
Service
Connector
Sensor Button
Fig. 8-9
Fig. 8-10
8-15
SM830194-04_Single_BigPAC.indb 15
2014/10/31 13:30:52
Summary of Contents for S-200PE1E8
Page 88: ...1 82 MEMO ...
Page 112: ...3 2 3 3 1 Outdoor Units Electric Wiring Diagram U 200PE1E8 U 250PE1E8 ...
Page 113: ...3 3 3 Schematic Diagram U 200PE1E8 U 250PE1E8 ...
Page 115: ...3 5 3 3 2 Indoor Units High Static Pressure Ducted Type S 200PE1E8A Electric Wiring Diagram ...
Page 116: ...3 6 3 3 2 Indoor Units High Static Pressure Ducted Type S 200PE1E8A Schematic Diagram ...
Page 117: ...3 7 3 3 2 Indoor Units High Static Pressure Ducted Type S 200PE1E8 Electric Wiring Diagram ...
Page 118: ...3 8 3 3 2 Indoor Units High Static Pressure Ducted Type S 200PE1E8 Schematic Diagram ...
Page 119: ...3 9 3 3 2 Indoor Units High Static Pressure Ducted Type S 250PE1E8 Electric Wiring Diagram ...
Page 120: ...3 10 3 3 2 Indoor Units High Static Pressure Ducted Type S 250PE1E8 Schematic Diagram ...
Page 129: ...4 9 4 4 3 Outdoor Unit Filter PCB FIL C906VH8 ...
Page 130: ...4 10 4 4 4 Outdoor Unit HIC Board HIC C906VH8 ...
Page 136: ... MEMO 4 16 ...
Page 154: ... MEMO 5 18 ...
Page 164: ... MEMO 6 10 ...
Page 180: ... MEMO 7 16 ...
Page 197: ...201411 ...