2
2
2-21
2-21-3. Checking Indoor unit addresses
Use the remote controller to check the addresses of the indoor
units. Press and hold the
button and
button for 4
seconds or longer (simple settings mode, “ALL” appears on the
remote controller). Then press the
button and select the
indoor address.
(For the system addresses of the No. 1 outdoor unit, each time the
button is pressed, the address changes as follows: 1-1, 1-2, ...)
The indoor unit fan operates only at the selected indoor unit.
Confirm the indoor unit address. (For the system addresses of
the No. 2 outdoor unit, the displayed addresses are 2-1, 2-2, ...)
Press the
button again to return to the normal remote
controller mode.
Fig. 2-18
2-21-4. Indicating (marking) the Indoor and Outdoor unit combination number
Indicate (mark) the number after automatic address setting is completed.
(1) So that the combination of each indoor unit can be easily checked when multiple units are installed, ensure
that the indoor and outdoor unit numbers correspond to the system address number on the outdoor unit
control PCB, and use a magic marker or similar means which cannot be easily removed to indicate the
numbers in an easily visible location on the indoor units (near the indoor unit nameplates).
Example : (Outdoor) 1 – (Indoor) 1
(Outdoor) 2 – (Indoor) 1
(2) These numbers will be needed for maintenance. Be sure to indicate them.
Installing the Remote Controller
Refer to Instruction Manual attached to the optional Wireless Remote Controller.
SM830194-04_Single_BigPAC.indb 21
2014/11/04 13:45:16
Summary of Contents for S-200PE1E8
Page 88: ...1 82 MEMO ...
Page 112: ...3 2 3 3 1 Outdoor Units Electric Wiring Diagram U 200PE1E8 U 250PE1E8 ...
Page 113: ...3 3 3 Schematic Diagram U 200PE1E8 U 250PE1E8 ...
Page 115: ...3 5 3 3 2 Indoor Units High Static Pressure Ducted Type S 200PE1E8A Electric Wiring Diagram ...
Page 116: ...3 6 3 3 2 Indoor Units High Static Pressure Ducted Type S 200PE1E8A Schematic Diagram ...
Page 117: ...3 7 3 3 2 Indoor Units High Static Pressure Ducted Type S 200PE1E8 Electric Wiring Diagram ...
Page 118: ...3 8 3 3 2 Indoor Units High Static Pressure Ducted Type S 200PE1E8 Schematic Diagram ...
Page 119: ...3 9 3 3 2 Indoor Units High Static Pressure Ducted Type S 250PE1E8 Electric Wiring Diagram ...
Page 120: ...3 10 3 3 2 Indoor Units High Static Pressure Ducted Type S 250PE1E8 Schematic Diagram ...
Page 129: ...4 9 4 4 3 Outdoor Unit Filter PCB FIL C906VH8 ...
Page 130: ...4 10 4 4 4 Outdoor Unit HIC Board HIC C906VH8 ...
Page 136: ... MEMO 4 16 ...
Page 154: ... MEMO 5 18 ...
Page 164: ... MEMO 6 10 ...
Page 180: ... MEMO 7 16 ...
Page 197: ...201411 ...