![Panasonic S-200PE1E8 Technical Data & Service Manual Download Page 85](http://html.mh-extra.com/html/panasonic/s-200pe1e8/s-200pe1e8_technical-data-and-service-manual_269829085.webp)
1-79
1
1
Attach the heat exchanger
pipe thermistor in the middle
of each pass-line (pipe) in
the heat exchanger.
The thermistor is fixed
in band.
Then, it must not make
tension to the wire.
Cover the aluminum tape
with thermal insulation.
And also cover sensor
(copper portion) with
thermal insulation completely.
Installation
Thermistor for Liquid pipe and Heat exchanger pipe middle
Liquid pipe thermistor
Heat exchanger pipe thermistor
Attach the liquid pipe thermistor
to the liquid pipe located in the
lowest position after distributer
in heat exchanger.
Cover the thermistor
and pipe with
aluminum tape.
Cover the thermistor
and pipe with
aluminum tape.
Thermal insulation and
wiring are fixed in two
bands.
Cover the aluminum
tape with thermal
insulation.
Installation of Strainer (Field supplied)
Attach the strainer to the side of the outdoor unit for Gas & Liquid piping.
(See the “System Overview” on previous page.)
Attachment of NOTES Label (Supplied parts)
Please be sure to apply the NOTES label at the designated area of the outdoor unit when cutting a jumper
wire on the circuit board.
NOTES
Sec1.indd 79
2014/11/07 10:28:11
Summary of Contents for S-200PE1E8
Page 88: ...1 82 MEMO ...
Page 112: ...3 2 3 3 1 Outdoor Units Electric Wiring Diagram U 200PE1E8 U 250PE1E8 ...
Page 113: ...3 3 3 Schematic Diagram U 200PE1E8 U 250PE1E8 ...
Page 115: ...3 5 3 3 2 Indoor Units High Static Pressure Ducted Type S 200PE1E8A Electric Wiring Diagram ...
Page 116: ...3 6 3 3 2 Indoor Units High Static Pressure Ducted Type S 200PE1E8A Schematic Diagram ...
Page 117: ...3 7 3 3 2 Indoor Units High Static Pressure Ducted Type S 200PE1E8 Electric Wiring Diagram ...
Page 118: ...3 8 3 3 2 Indoor Units High Static Pressure Ducted Type S 200PE1E8 Schematic Diagram ...
Page 119: ...3 9 3 3 2 Indoor Units High Static Pressure Ducted Type S 250PE1E8 Electric Wiring Diagram ...
Page 120: ...3 10 3 3 2 Indoor Units High Static Pressure Ducted Type S 250PE1E8 Schematic Diagram ...
Page 129: ...4 9 4 4 3 Outdoor Unit Filter PCB FIL C906VH8 ...
Page 130: ...4 10 4 4 4 Outdoor Unit HIC Board HIC C906VH8 ...
Page 136: ... MEMO 4 16 ...
Page 154: ... MEMO 5 18 ...
Page 164: ... MEMO 6 10 ...
Page 180: ... MEMO 7 16 ...
Page 197: ...201411 ...