7
7
7-2. List of Simple Setting Items
Item code
Item
Setting data
No.
Description
Filter sign ON time
(filter life time)
0000
Not displayed
0001
150 hours
0002 2,500 hours
0003
5,000 hours
0004 10,000 hours
0005
Use the filter clogging sensor.
Degree of filter fouling
0000
Standard (setting at time of shipping)
0001
Highly fouled
(Filter sign ON time is reduced to one-half the set time.)
Central control
address
0001
Central control address 1
0002 Central control address 2
0003
Central control address 3
0064 Central control address 64
0099
No central control address set (setting at time of shipping)
Operating mode
priority change
0000
Normal ( setting at time of shipping)
0001
Priority
Fan speed when
heating thermostat is
OFF
Compressor ON
Compressor OFF
0000
Lo 1 min., LL 3 min.
LL
0001
Lo
LL
0002
LL
LL
0004
Lo 1 min., LL 3 min.
Lo
0005
Lo
Lo
0006
LL
Lo
Heating intake
temperature shift
0000
No shift
0001
Shifts intake temperature 1 °C down.
0002 Shifts intake temperature 2 °C down.
0003
Shifts intake temperature 3 °C down.
0004 Shifts intake temperature 4 °C down.
0005
Shifts intake temperature 5 °C down.
0006
Shifts intake temperature 6 °C down.
Electric heater
installation
0000
No heater
0001
Heater installed
Humidifying when
heater thermostat is
OFF
0000
No (setting at time of shipping)
0001
Yes
Permit/prohibit
automatic
heating/cooling
0000
Permit
0001
Prohibit
Cool-only
0000
Normal
0001
Cool only (Set “1” for item code OD.)
NOTE
• In order to avoid water leakage and damage to the fan, do not set for humidifying when the thermostat is OFF
unless a vaporizing humidifier is used.
• Consider the device purpose and type when changing the settings. Incorrect settings may result in malfunction.
• Do not change any setting data that does not appear in this list.
7-3
SM830194-04_Single_BigPAC.indb 3
2014/11/14 14:38:33
Summary of Contents for S-200PE1E8
Page 88: ...1 82 MEMO ...
Page 112: ...3 2 3 3 1 Outdoor Units Electric Wiring Diagram U 200PE1E8 U 250PE1E8 ...
Page 113: ...3 3 3 Schematic Diagram U 200PE1E8 U 250PE1E8 ...
Page 115: ...3 5 3 3 2 Indoor Units High Static Pressure Ducted Type S 200PE1E8A Electric Wiring Diagram ...
Page 116: ...3 6 3 3 2 Indoor Units High Static Pressure Ducted Type S 200PE1E8A Schematic Diagram ...
Page 117: ...3 7 3 3 2 Indoor Units High Static Pressure Ducted Type S 200PE1E8 Electric Wiring Diagram ...
Page 118: ...3 8 3 3 2 Indoor Units High Static Pressure Ducted Type S 200PE1E8 Schematic Diagram ...
Page 119: ...3 9 3 3 2 Indoor Units High Static Pressure Ducted Type S 250PE1E8 Electric Wiring Diagram ...
Page 120: ...3 10 3 3 2 Indoor Units High Static Pressure Ducted Type S 250PE1E8 Schematic Diagram ...
Page 129: ...4 9 4 4 3 Outdoor Unit Filter PCB FIL C906VH8 ...
Page 130: ...4 10 4 4 4 Outdoor Unit HIC Board HIC C906VH8 ...
Page 136: ... MEMO 4 16 ...
Page 154: ... MEMO 5 18 ...
Page 164: ... MEMO 6 10 ...
Page 180: ... MEMO 7 16 ...
Page 197: ...201411 ...