9-8. Suspending the Indoor Unit
It is important that you use extreme care in supporting the indoor unit inside the
ceiling. Ensure that the ceiling is strong enough to support the weight of the unit.
Before hanging the unit, test the strength of each attached suspension bolt.
(1) When placing the unit inside the ceiling, determine the pitch
of the suspension bolts referring to the dimensional data
given previously. (Figs. 1-33 and 1-34)
Tubing must be laid and connected inside the ceiling when
suspending the unit. If the ceiling is already constructed,
lay the tubing into position for connection to the unit before
placing the unit inside the ceiling.
(2) Screw in the suspension bolts allowing them to protrude
from the ceiling as shown in Fig. 1-35.
(Cut the ceiling material, if necessary.)
(3) Suspend and fix the indoor unit using the 2 hexagonal nuts
(field supply) and special washers (supplied with the unit)
as shown in Fig. 1-37.
3. Installing the Refrigerant Tubing
The size of the refrigerant tubing is as shown in Table 1-5.
Table 1-9
Type 200
Type 250
Gas tube
(mm)
ø25.4
(Brazing connection)
ø25.4
(Brazing connection)
Liquid tube
(mm)
ø9.52
(Flare connection)
ø12.7
(Flare connection)
When brazing the gas tubing, cool the tubing with dampened
shopcloths as you work, as shown in Fig. 1-38, to protect the
unit’s thermistor from the heat generated by brazing.
ø25.4
ø 25.4
The tube connector that comes with the Type 250 indoor unit
cannot be used in combination with this outdoor unit.
Use in combination with the U-250PE1E8.
Depending on the ceiling type:
Insert suspension bolts as shown in Fig. 1-35
or
Use existing ceiling supports or construct
a suitable support as shown in Fig. 1-36.
Fig. 1-35
Hole-in-anchor
Hole-in-plug
Concrete
Insert
Suspension bolt (M10 or 3/8”)
(field supply)
Ceiling tiles
Ceiling support
Fig. 1-36
Suspension bolt
Hexagonal nuts
and washers
(2 sets)
Fig. 1-37
20 – 50 mm
Brazing
Dampened shopcloths
Inter-unit
gas tubing
Thermistor (Indoor unit)
Fig. 1-38
WARNING
Sec1.indd 66
2014/11/07 10:28:08
Summary of Contents for S-200PE1E8
Page 88: ...1 82 MEMO ...
Page 112: ...3 2 3 3 1 Outdoor Units Electric Wiring Diagram U 200PE1E8 U 250PE1E8 ...
Page 113: ...3 3 3 Schematic Diagram U 200PE1E8 U 250PE1E8 ...
Page 115: ...3 5 3 3 2 Indoor Units High Static Pressure Ducted Type S 200PE1E8A Electric Wiring Diagram ...
Page 116: ...3 6 3 3 2 Indoor Units High Static Pressure Ducted Type S 200PE1E8A Schematic Diagram ...
Page 117: ...3 7 3 3 2 Indoor Units High Static Pressure Ducted Type S 200PE1E8 Electric Wiring Diagram ...
Page 118: ...3 8 3 3 2 Indoor Units High Static Pressure Ducted Type S 200PE1E8 Schematic Diagram ...
Page 119: ...3 9 3 3 2 Indoor Units High Static Pressure Ducted Type S 250PE1E8 Electric Wiring Diagram ...
Page 120: ...3 10 3 3 2 Indoor Units High Static Pressure Ducted Type S 250PE1E8 Schematic Diagram ...
Page 129: ...4 9 4 4 3 Outdoor Unit Filter PCB FIL C906VH8 ...
Page 130: ...4 10 4 4 4 Outdoor Unit HIC Board HIC C906VH8 ...
Page 136: ... MEMO 4 16 ...
Page 154: ... MEMO 5 18 ...
Page 164: ... MEMO 6 10 ...
Page 180: ... MEMO 7 16 ...
Page 197: ...201411 ...