91
Installation Manual
■
Preparation
• See 7-2 and switch to the Parameter Item Selection mode showing the initial display [no4.13].
■
Operation Procedure
• While [no4.13] is displayed, press "MENU (ENTER)" to switch to the Parameter Display mode.
• While the Parameter Display mode is selected, press "DATA(▲)" or "CLOCK(▼)" and select the parameter item.
Then press "MENU (ENTER)" to switch to the Parameter Setting mode. Or press "ON/OFF (CANCEL)" to return
to the Parameter Item selection.
• While the Parameter Setting mode is selected and digits are blinking, press "DATA(▲)" or "CLOCK (▼)" and
adjust the parameter level.
• After the adjustment of the parameter level, press "MENU (ENTER)" to fix the parameter level. Or press
"ON/OFF (CANCEL)" to cancel. Then return the Parameter Display mode.
• After returning the Parameter Display mode, press "ON/OFF (CANCEL)" to return the Parameter Item Selection.
Parameter Item
Selection
Parameter
Setting Mode
Parameter
Display Mode
or
Characteristic
Power(P1)
CosΦ of Point1
(λ1)
Source or Sink
Setting(λ1)
Characteristic
Power(P2)
CosΦ of Point2
(λ2)
Source or Sink
Setting(λ2)
Characteristic Power
(P1)
CosΦ of Point1
(λ1)
Source or Sink Setting
(λ1)
Characteristic Power
(P2)
CosΦ of Point2
(λ2)
Source or Sink Setting
(λ2)
Characteristic
Power Factor Curve
or
or
or
or
or
or
7-18. Reverse Power Mode Setting
In this setting mode. thepropriety of reverse power flow from the storage battery system can be set.
However, if there in an instruction from DRED, it gives priority to the instruction of DRED not set here.
Parameter Item
Default Set Point
Range
Parameter Selection
Display
0
0:enable
1:disenable
Reverse Power
Mode Setting
Table DRM Mode List
■
Preparation
• See 7-2 and switch to the Parameter Item Selection mode showing the initial display [no4.14].
■
Operation Procedure
• While [no4.14] is displayed, press "MENU (ENTER)" to switch to the Parameter Display mode.
• While the Parameter Display mode is selected, press "MENU (ENTER)" to switch to the Parameter Setting mode.
Or press "ON/OFF (CANCEL)" to return to the Parameter Item selection.
• While the Parameter Setting mode is selected and the digit is blinking, press "DATA(▲)" or "CLOCK (▼)" and set
"0" (enable) or "1" (Disenable).
• After the selection, press "MENU (ENTER)" to store the data. Or press "ON/OFF (CANCEL)" to cancel. Then
return the Parameter Display mode.
• After returning the Parameter Display mode, press "ON/OFF (CANCEL)" to return the Parameter Item Selection.
Reverse Power
Mode Setting
Reverse Power Mode
Setting
Reverse Power Mode
Parameter Display Mode
Parameter Item Selection
Parameter Setting Mode
or
or
Australia/New Zealand