56
Installation Manual
Reference: How to check the voltage with the Grid terminal
■
If the AC Voltage Status or DC Voltage Status are Showing an Error
4-3. Checking DC/AC Voltage Energization
■
Operation Procedure
•
Press "CLOCK (▼)"+"DATA (▲)" for three seconds in the normal state to open the status selection mode.
•
Press "DATA (▲)" or "CLOCK (▼)" to display the system status [S1].
•
The second digit indicates the AC voltage status, and the third digit indicates the DC voltage status.
•
[ ] appears in the normal state, and [ ] appears in the error state. Make sure that the displays for the 2nd and
3rd digits turn to [ ].
•
•
The DC protector or the AC protection device may be turned OFF.
Check that the DC protector and the AC protection device are turned ON.
If you do not set the destination setting, AC voltage status (2nd digit) will be NG (Error).
Please check again after setting the grid operator mode (Chapter 7).
•
Refer to Chapter "Installation", check that the battery is wired correctly.
•
Refer to Chapter "Installation", check that the wiring on the AC side is wired correctly.
Terminal levers have holes for measurement in the upper part. Insert the test bar of a voltmeter into the hole to
measure the voltage.
Stopped (Grid-connected)
Stopped (Stand-alone)
Status 2
Status 1
Status 3
ュモヵモ
ヤロヰヤレ
or
ュモヵモ
ヤロヰヤレ
or
ュモヵモ
ヤロヰヤレ
or
Status Selection
Normal State
ヰワバ
ヰョョ
ヤモワヤユロ
1 sec
3 sec
ヤロヰヤレ
+
: OK(Normal state)
: NG (Error state)
1st digit : Network Adaptor Communication status
2nd digit : AC Voltage Status
3rd digit : DC Voltage Status
*5,',17(5$&7,9(DF9
by qualified personnel.
date/time notified by the Network Adaptor is given higher priority.
5. Setting Date/Time
5-1. Date/Time
The date/time needs to be set for this system to operate normally. The Programmed charge/discharge time mode
cannot work correctly if the date/time is not set correctly.
● If the ALARM LED is blinking in green, the date/time has not yet been set. Set the date/time.
● The date/time setting is required when not connecting to the Network Adaptor.
The scheduled operation mode cannot work correctly if the date/time is not set.
● When connecting with the Network Adaptor, the
However, the date/time needs to be set manually as an initial setting.
● The work must be performed
5-2. Date/Time Setting
■
Preparation
•
See the list of commands in P.52 to switch to normal state conditions.
■
Operation Procedure
Display of Setting
Normal State
Stopped (Stand-alone)
Date/Time Setting Mode
Year (initial)
Month
Day
Hour
Minute
3 sec
Automatic
or
or
or
or
or
Stopped (Grid-connected)
1 sec