19
User's Manual
■ Do not plug the following electric equipment into the output connected to the Stand-alone Socket-outlet:
8-7 Stand-alone Operation Start Setting
Prohibited
• Any medical devices or security equipment
• Equipments that might lose information during power failure such as desktop computer.
• Kerosene heaters or any heating equipment that starts automatically when the power supply is restored.
The product will stop operating when the power consumption of the electrical equipment plugged into the
outlet connected to the back-up socket exceeds the maximum output power of the product.
Never connect any electrical equipment that may pose a threat to human life or properties in the event
of a power failure.
• In this setting, Stand-alone operation can be selected from manual start or automatic start when grid power stopped.
Default set is "manual start".
• The manual start (CH-01) is the mode to be manually switched to Stand-alone operation from the grid operation.
Please see the Chapter 5
• The automatic start (CH-02) is the mode to be automatically switched to Stand-alone operation from the grid
operation.
• Refer to 8-1 to Stand-alone operation start setting in the user setting mode [no- 6].
• Pressing "MENU (ENTER)" will switch to the display mode. The Stand-alone operation start setting will be displayed.
• Press "MENU (ENTER)" in the display mode to switch to the setting mode. The current setting will blink.
• Press "DATA (▲)" and "CLOCK (▼)" to select from manual start (CH-01) or automatic start (CH-02) when grid
power stopped.
• Press "MENU" to set the data and switch to the display mode. Or pressing "ON/OFF (CANCEL)" to cancel the
setting and switch to the display mode.
• Press "ON/OFF (CANCEL)" in the display mode to return to the User setting mode [no -6].
■
Operation
User Setting Mode
Stand-alone Operation
Start Setting
Show the
current setting
CH-01:Manual start
CH-02:Automatic start
Press
"
DATA (▲)
"
or
"
CLOCK (▼)
"
to set CH-01 or CH-02.
Stand-alone Operation Start Setting
or
Display Mode
Setting Mode
Notice:
* If there is a switch for the Stand-alone Socket-output, please set "OFF" normally.
* When the grid power recovers the system does not connect the grid automatically. The system will continue to
output the power using the battery energy. See chapter 5 and switch to the grid operation.