9
Installation Manual
be configured with different specifications.
For Storage battery system
: AC230V 16A trip (TYPE C)
For Network Adaptor
: AC230V 10A trip (TYPE C)
For STAND-ALONE Socket outlet : AC230V 16A trip (If necessary)*
In compliance with the law and regulations, select RCD "type" and "rated sensitive leakage current".
System Configuration
Storage
battery
system
Network
Adaptor
COM
DRM
To DRED
×
No connect
SYS
COM
CT
CT
Point of
Supply
Main
switch
Home
Load
TN or TT
system
L1
L N
N1
PE
PE
N
PE
L N PE
STAND-ALONE
Socket-outlet
(Type-02)
Switch board
Turn off these protection
devices in an emergency.
◎
Installation of Single System
CT/COM/DRM/SYSTEM line is SELV circuit.
Grid-interactive Line
Grid Line
Stand-alone Line
DRM Line
SYSTEM Line
max. 50 m
max. 50 m
CAT5e (10BASE-T/100BASE-TX)
PVC Flexible Cable 2C 0.75mm
2
*
Please use copper wire cables.
* This wiring system chart is only a typical example and may
The wiring system can be designed as necessary in accordance with wiring rules.
* Network Adaptor and/or DRED are not installed on some systems depending on contractual coverage.
*
●
Protection Device
In compliance with the law and regulations, please select and install protection devices with reference to the
following.
Circuit-breaker
Select and install the circuit breaker for protection of AC over current.
RCD
* In this product, between the DC side of battery and the AC side is insulated.
* This product is equipped with STAND-ALONE breaker "Type-AC". If the circuit breaker other than "Type-AC" is required,
please install the appropriate circuit breaker for STAND-ALONE Socket-outlet in accordance with the law and regulations.
●
Wiring
Conductors
Cable/Wire Size
Cable/Wire Length
PVC Circular Cable 2C+E 2.5 mm
2
max. 50 m
PVC Circular Cable 2C+E 1.5 mm
2
max. 50 m
PVC Circular Cable 2C+E 2.5 mm
2
max. 50 m
CT Line
PVC Flexible Cable 2C 0.75 mm
2
max. 50 m
COM Line
PVC Flexible Cable 2C 0.75 mm
2
max. 50 m
Protection
device for
Storage
battery
system
Protection
device for
Network
Adaptor
Turn off these protection
devices for these products
in an emergency.
This is an example diagram for 3-phase 4-wire system Refer to "Protection device" and "wiring" in the previous page.
N
PE
◎
Installation of Multiple System
STAND-ALONE
Socket-outlet
(Type-02)
STAND-ALONE
Socket-outlet
(Type-02)
STAND-ALONE
Socket-outlet
(Type-02)
Main
switch
Protection
device
Point of
Supply
TN or TT
system
CT
CT
L N
PE
N
PE
L N
PE
Distribution board
Storage
battery
system
Network
Adaptor
COM
DRM
To DRED
SYS
COM
L1
N1
PE
Protection
device for
Storage
battery
system
Protection
device for
Network
Adaptor
CT
CT
L N
PE
N
PE
L N
PE
Distribution board
Storage
battery
system
Network
Adaptor
COM
DRM
To DRED
SYS
COM
L1
N1
PE
Protection
device for
Storage
battery
system
Home
Load
Home
Load
Home
Load
Protection
device for
Network
Adaptor
CT
CT
L N
PE
N
PE
L N
PE
Distribution board
Storage
battery
system
Network
Adaptor
COM
DRM
To DRED
SYS
COM
L1
N1
PE
Protection
device for
Storage
battery
system
Protection
device for
Network
Adaptor
Main
switch
Main
switch
Main
switch
*
*
*
*
*
*
*
Summary of Contents for LJ-NA02
Page 6: ...Installation Manual Installation ...
Page 49: ...Installation Manual Setup ...
Page 100: ...Installation Manual ...