Photoelectric smoke detector. Replaces 4352, see above. Like
4352 but 4452 has a little different design than the 4352
detector (see 4401 above) and the smoke chamber net has even
smaller holes. This will keep insects and particles
smoke particles out of the chamber.
4375
Heat detector. Fixed temperature heat detector, 60°C, class
A2S
(static response temp. range 54-70°C), latching.
Min./
typical
/max. ambient temp. -10/
+25
/+40°C.
The detector has unleaded soldering. Has replaced 6275.
To be plugged in a base 2324.
4376
Heat detector. Fixed temperature heat detector, 80°C, class
BS
(static response temp. range 69-85°C), latching.
Min./
typical
/max. ambient temp. -10/
+40
/+60°C.
The detector has unleaded soldering. Has replaced 6276.
To be plugged in a base 2324.
6295
Heat detector: Enclosed (IP67)
42
. Fixed temperature (57°C)
heat detector, class
A2 S
(static response temp. range 54-70°C),
latching. Min./
typical
/max. ambient temp. -40/
+25
/+50°C.
Built-in LED that is lit to indicate that the detector has
generated fire alarm. Terminals for ext. LED 2217 / 2218.
6296
Heat detector: Enclosed (IP67)
43
. Fixed temperature (72°C)
heat detector, class
B S
(static response temp. range 69-85°C),
latching. Min./
typical
/max. ambient temp. -40/
+40
/+65°C.
Built-in LED that is lit to indicate that the detector has
generated fire alarm. Terminals for ext. LED 2217 / 2218.
6297
Heat detector: Enclosed (IP67). Fixed temperature (87°C) heat
detector, class
C S
(static response temp. range 84-100°C),
latching. Min./
typical
/max. ambient temp. -40/
+55
/+80°C.
Built-in LED that is lit to indicate that the detector has
generated fire alarm. Terminals for ext. LED 2217 / 2218.
6298
Heat detector: Enclosed (IP67). Fixed temperature (117°C) heat
detector, class
E S
(static response temp. range 114-130°C),
latching. Min./
typical
/max. ambient temp. -40/
+85
/+110°C.
Terminals for ext. LED 2217 / 2218 (to indicate that the
detector has generated fire alarm).
NOTE!
No built-in LED.
42
As from July 2013, this detector holds the ATEX classification:
Ex II 3 G Ex ic IIC T5 Gc, Ex II 3 D Ex ic IIIC T100°C Dc,
-40°C < T
a
< 50°C
.
43
As from July 2013, this detector holds the ATEX classification:
Ex II 3 G Ex ic IIC T5 Gc, Ex II 3 D Ex ic IIIC T100°C Dc,
-40°C < T
a
< 65°C
.