EBL128 Planning Instructions V2.0.x
87
Figure 16. The EBLWin dialog box "Interlocking Combination".
Logical Name
: Displayed in the EBLWin Tree and List views.
Default name can be changed when wanted / required.
Area
and
Point
: Each "Interlocking Combination" is presented as
Area-Point (compare with Zone-Address). Area numbers 1-99 are
possible to use and Point numbers 1-99 are possible to use.
Available interlocking outputs
list displays all the previous
programmed outputs, Type = "Interlocking Output".
Available interlocking inputs
list displays all the previous
programmed inputs with the Triggered by alternative (trigger
condition) 10 = "Interlocking Input".
Select one output and one input in the list respectively.
90
Press
Select
and the selected output and input will be shown in the
Selected
output
and
Selected input
field respectively.
Text
= Interlocking text to be shown in the menu H9/C1. Can be
written in this field or in the "Texts" dialog box, see chapter "Creating
the alarm texts via EBLWin", page 114.
Buzzer
checked = activated interlocking input will turn on the
EBL128 buzzer (0.8 / 0.8 sec.)
91
. The buzzer can be silenced. It will
be automatically turned on again, if a new interlocking input is
activated.
Latched output
checked = Output reset has to be performed via menu
H9/C3. (Automatically output reset will not take place when the
control expression becomes false.).
Fault
checked = Fault detection ON.
90
Output / Input parent will then show in which unit the output / input
respectively is situated.
91
Priority order: Fire alarm – Pre-warning - Interlocking - Fault.