EBL128 Planning Instructions V2.0.x
47
levels are available. For each level an output control expression
and a sound type is programmed (via EBLWin). For more
technical data, see the Product Leaflet.
The COM loop address is set with the Address setting tool 3314
/ 4414. The unit has an address label on which the programmed
COM loop address can be written. (The detector has its own
COM loop address set via the Address setting tool.)
The Address setting tool is also used for mode setting:
NORMAL mode
: Used for 3379 in system EBL128.
2330 mode
: Not used in system EBL128.
2312 mode
: Not used in system EBL128.
NOTE!
See also chapter "Limitations", page 174.
4380
Addressable beacon. 4380 is a visual alarm device of type A
for indoor use. All electronics, the LEDs and the lens are
mounted in a red ABS housing. The beacon comes with a
shallow base (IP21C). A deep base (4382) is an option which
gives the beacon a higher IP protection (IP33C). 4380 is power
supplied via the COM loop, i.e. the number of beacons is
depending on the type and number of other units connected to
the COM loop but max. 10.
The light output is 1 Cd and the flash rate is 1 Hz. For more
technical data, see the Product Leaflet.
The COM loop address is set with the Address setting tool 3314
/ 4414. The unit has an address label on which the programmed
COM loop address can be written.
The Address setting tool is also used for mode setting:
NORMAL mode
: Used for 4380 in system EBL128.
2330 mode
: Not used in system EBL128.
2312 mode
: Not used in system EBL128.
4383
Light indicator. 4383 is a light indicator used as a complement
to audible alarm devices. It is of type A for indoor use. All
electronics and the eight red LEDs (visible 360°) are mounted
in a transparent ABS housing. Flash rate 1 Hz. 4383 is power
supplied via the COM loop, i.e. the number of indicators is
depending on the type and number of other units connected to
the COM loop. The light indicator is plugged in an analog
detector base 3312xx (3379 / 4313) and an analog detector is
plugged in the light indicator. A control expression for
activation has to be programmed, like for a programmable
output or alarm device. It takes one COM loop address. For
more technical data, see the Product Leaflet.
The COM loop address is set with the Address setting tool 3314
/ 4414. The unit has a label for the COM loop address and
another label for the detector's COM loop address.
The Address setting tool is also used for mode setting:
NORMAL mode
: Used for 4383 in system EBL128.
2330 mode
: Not used in system EBL128.
2312 mode
: Not used in system EBL128.