Panasonic Eco Solutions Nordic AB
MEW01622
Rev: -
EBL128 Planning Instructions V2.0.x
22
Logic, i.e. Normally open (high resistance, 3K3, when supervised)
or
Normally closed (low resistance, 680R, when supervised)
Additional information depending on selected type
See also chapter "Programmable inputs", page 63.
4.6
24 V DC power supply outputs
The two 24 V DC
16
outputs can be used for:
Power supply of routing equipment (fire brigade tx / fault tx).
Max. 200 mA (Fuse F7).
Power supply of external equipment, e.g. ext. FBP 1826 / 1828,
AAU 1735 / 1736, EPU 1728, etc. Max. 500 mA (Fuse F9
17
).
Connections to "J1:11-12 & 13-14" according to drawing 128-22.
4.7
RS232 interfaces
The two interfaces can be used for:
EBLWin (PC program). (9 ways female "D" connector)
Web-server II 1598. (3 ways Molex connector)
Connections to "J3" & "J5" according to drawing 128-25.
4.8
RS485 transceiver (option)
There is a socket on the main board 4556 where an optional RS485
transceiver communication module 4552 can be mounted. This
transceiver provides an interface (screw terminals J1:15-16) for up to
eight Display Units, i.e. ext. FBP 1826
18
/ 1828 and/or AAU 1735 /
1736 and/or EPU 1728 running in
S/W mode
xxxx – 1587
19
. The
data rate in this mode is 9600 baud and max. cable length is 1200 m.
Connections to "J1:15-16" according to drawing 128-23.
On the RS485 serial line can as an alternative be connected up to eight
German Fire Brigade Control Panels (Feuerwehr-Bedienfeld)
FBF
2003
3
and/or German Fire Brigade Indicator Panels (Feuerwehr-
Anzeigetableau)
FAT 2002
3
.
4.9
Power supply
Connectors for the built-in power supply units:
Power supply (Rectifier) 230 V AC /
24 V DC
(Two tab
terminals, 6.35x0.8 mm, +24V / 0V)
16
Regarding
system voltage
, see chapter "Technical data", page 143.
17
Fuse F9 is also for the 24 V DC internal power supply output for Web-
server 1598, see drawing 128-25.