Panasonic Eco Solutions Nordic AB
MEW01622
Rev: -
EBL128 Planning Instructions V2.0.x
29
5.5
I/O Matrix board 4582
A special type of expansion board that can only be used together with
an
Application board
(Fan, Generic or Zone).
Up to four 4582 boards can be used and up to eight if no expansion
boards of type 4580, 4581 or 4583 are used.
The I/O Matrix board makes it possible for any retailer to manufacture
and connect three different types of "Application boards" to EBL128
via the COM loop.
I/O
Matrix
board
4582
I/O
Matrix
board
4582
I/O
Matrix
board
4582
EBL512
C.i.e.
COM loop
24 V DC
Type:
Generic
Zone
Fan
Generic
c.i.p. board
Fan c.i.p. board
Zone c.i.p. board
Application
boards:
Fan c.i.p.
Mimic panel / New Zealand i.p.
Zone c.i.p.
No. 0
No. 1
No. 3
NOTE!
Up to 16 I/O Matrix board 4582 per EBL512 C.i.e.
Up to 4 (No. 0-3) I/O Matrix board 4582 per COM loop.
Up to 4 I/O Matrix boards type Generic and/or Zone per EBL512 C.i.e.
Figure 6. I/O Matrix board 4582 application
overview
. The
COM loop and 24 V DC are internally connected to the 4582
board.
The I/O Matrix board (80 x 63 mm) is plugged ("piggy back"
connection) to the Application board respectively and has 16 inputs
and 48 outputs. The COM loop and 24 V DC is connected to
Application board.
Three different
application board types
can be selected via jumpers
(
JP4-JP5
) on the I/O Matrix board:
Generic
control and indicating panel (Mimic panel alt. New Zealand
indication panel), with 16 inputs (any input trigger condition can be
used) and 48 outputs (any output trigger condition can be used).
Fan
control and indicating panel, for four Fan control panels, each
with six LED:s (On / Auto / Off / Running / Stopped / Fault) and three
push buttons (On / Auto / Off). One "Reset" switch. Can be used for
a "Supply air fan" or a "Standard fan".
Zone
control and indicating panel, with outputs and inputs for 16 zone
LEDs (Alarm / Fault / Disabled) and 16 push buttons (Disable / Re-
enable).
There is no COM loop address to be set. Instead, the
expansion
board address
(0-7) is set with jumpers (
JP1-JP3
) on the I/O Matrix
board respectively.
Up to four I/O Matrix boards can be used but up to eight if no
expansion boards of types 4580, 4581 and 4583 are used.
Note!
Max.
two I/O Matrix boards of the types Generic and Zone respectively.