Panasonic Eco Solutions Nordic AB
MEW01622
Rev: -
EBL128 Planning Instructions V2.0.x
28
Type, i.e. output for Control, Alarm devices, etc.
Output signal period (steady, pulse, delay, etc.)
Supervised / Not supervised
27
Logic, i.e. normally low (default)
or
normally high (24 V DC)
28
.
Control expression (containing one or more trigger conditions)
One to five 33K resistors can be connected. When the connections are
finished, a calibration has to be performed. Calibration value has to
be in the range 4K7-50K. See also the EBL128 Operating Instructions
chapter "Calibration of supervised outputs (menu H5/A1)".
Voltage
Output 0
(J1:1-2): max. 200 mA (Fuse F1). "E"
(Brandmeldung)
Voltage
Output 1
(J1:5-6): max. 200 mA (Fuse F2). "G"
FSK öffnen
See also chapter "Programmable outputs", page 70.
Output 2 has to be programmed
via EBLWin regarding:
Type, i.e. output for Control, Alarm devices, etc.
Output signal period (steady, pulse, delay, etc.)
Logic, i.e. normally open (default)
or
normally closed.
Control expression (containing one or more trigger conditions)
Output 2
(J1:11-12): Normally open (high resistance, 3K3) or
Normally closed (low resistance, 680R). German extinguishing
system
(Löschanlage)
.
See also chapter "Programmable outputs", page 70.
Input 0-4 has to be programmed
via EBLWin regarding:
Type ("trigger condition")
Supervised / Not supervised
Logic, i.e. Normally open (high resistance, 3K3, when supervised)
or
Normally closed (low resistance, 680R, when supervised)
Additional information depending on selected type
Input 0
(J1:3-4): Fire alarm routing equipment fault
(Melder
quittung)
Input 1
(J1:7-8): German key cabinet
(FSK rückmeldung)
Input 2
(J1:9-10): German key cabinet
(FSK überwachung)
Input 3
(J1:13-14): German extinguishing system
(Löschanlage
ausgelöst)
Input 4
(J1:15-16): German extinguishing system
(Löschanlage
quittung)
See also chapter "Programmable inputs", page 63.
27
A normally high output can not be supervised. The supervision voltage is
1.5 – 3.7 V DC (depending on the number of supervision resistors) and the
polarity is reversed compared to an activated output.
28
Regarding
system voltage
, see chapter "Technical data", page 143.