Panasonic Eco Solutions Nordic AB
MEW01622
Rev: -
EBL128 Planning Instructions V2.0.x
25
5.1
Expansion board address setting
The expansion board address is set via jumpers on the expansion
board respectively.
Board
address
4580, 4581 and 4583
4582
JP2
JP3
JP4
JP1
JP2
JP3
0
Open
Open
Open
Open
Open
Open
1
Shunted
Open
Open
Shunted
Open
Open
2
Open
Shunted
Open
Open
Shunted
Open
3
Shunted
Shunted
Open
Shunted
Shunted
Open
4
Open
Open
Shunted
Open
Open
Shunted
5
Shunted
Open
Shunted
Shunted
Open
Shunted
6
Open
Shunted
Shunted
Open
Shunted
Shunted
7
Shunted
Shunted
Shunted
Shunted
Shunted
Shunted
Figure 5. Expansion boards 4580 - 4583. Jumpers for
expansion board address setting.
5.2
8 zones expansion board 4580
Up to four 4580 boards can be used.
Each board has to be programmed
via EBLWin regarding:
Address (set via the jumpers "JP2-JP4", see Figure 5 above.)
The 4580 board has eight conventional zone line inputs (0-7) intended
for conventional detectors. In the last alarm point on each zone line,
an end-of-line device has to be connected, depending on the selected
"Type of zone line input", see below.
Connections to "J1:1-16" and "J2" according to drawing 128-30.
Each zone line input has to be programmed
via EBLWin regarding:
Type of zone line input (see below), depending on detectors / end-
of-line device (capacitor or resistor), i.e. different threshold levels
etc.
Alarm at short circuit / Not alarm at short circuit (i.e. if short-
circuit on the zone line shall generate a fault or a fire alarm)
Zone (Address optional)
Fire alarm delay / No fire alarm delay
Text (Alarm text when required)
Alert annunciation time channel
Disablement time channel