EBL128 Planning Instructions V2.0.x
85
Output:
Voltage output
S0
Control expression:
Pre Warning Zone (10)
Explanation:
Pre-warning activated in zone no. 10 will
activate the output S0.
Example 2
Output:
Relay output
R0
Control expression:
General Control disabled
AND NOT
Door
Open
Explanation:
Controls disabled via menu H2/B7 will
activate the output R0 when the door in
EBL128 is not open (i.e. when it is closed).
Example 3
Output:
Voltage output
VO0
Control expression:
Fire Alarm Zone (23)
AND
Fire Alarm Zone
(24)
AND NOT
General Fault
Explanation:
Fire alarm activated in zone 23 and zone 24
will activate the output VO0 only if there are
no
faults in the system at the same time.
Example 4
Output:
Voltage output
S1
Control expression:
Consecutive Fire Alarm (10,10,10,19,
1
)
OR
Consecutive Fire Alarm (10,21,10,40,
1
)
Explanation:
Fire alarm activated by
one
of the alarm
points in zone 10 addresses 10-19 or by
one
of the alarm points in zone 10 addresses
21-40 will activate the output S1 (i.e. the
alarm point in zone 10 address 20 will not
activate the output S1).