Panasonic Eco Solutions Nordic AB
MEW01622
Rev: -
EBL128 Planning Instructions V2.0.x
171
26
Technical data
Voltage
Primary (V AC):
230
(176-264)
System (V DC): 24
167
Current consumption
Quiescent / active: See chapter "Current consumption", page 162
Ambient temperature (
o
C)
Operating: -5 to +40
Storage: -40 to +75
Ambient humidity (%RH)
max. 95, non condensing
Ingress protection rating
IP 32 (estimated)
Size H x W x D (mm)
511 x 416 x 123. See also drawing 128-01
Weight (kg)
12.2 (excl. batteries)
Colour
Metal cabinet: Aluminium & light grey (NCS S 1500-N / PMS
Cool Gray 2)
Approvals
EBL128 is fully compliant with the European standard
EN54 parts
2 and 4
and the front is fully
SS3654
compliant.
167
The rated output voltage is 24 V DC ± 1% for the main power source
(rectifier). Max. ripple 300 mVp-p. The rated output voltage is 21-30 V DC
for the second power source (back-up battery).
NOTE!
There will, however,
be voltage in the system down to a battery voltage of approx. 20.8 V when it
will be switched off in order not to damage the battery.