Learning function / Learning period
Detectors 4400 and 4401 can use a
Learning function
, i.e. Depending
on the local temperature changes and the local occurrence of smoke
where the detector is situated, each detector can after a
learning
period
adapt a more appropriate alarm algorithm than the default
(Normal) one, an
Area Alarm algorithm
.
127
See also page 124.
15.5.1
Area Alarm algorithms
Normal area is the default Area alarm algorithm for each detector.
There are four other
Area
alarm algorithms
that can be adapted after
the learning period:
Smoke – Steam area, is depending on occurrence of smoke, i.e.
level 1
=
S
[%/m] > half the fire alarm threshold level (S).
Heater area, is depending on rise of temperature, i.e.
level 2
=
deltaT
[°C/168 sec.] > 12 (approx. 4.3°C/min.).
Cooking – Welding area, is depending on occurrence of smoke
together with rise of temperature, i.e.
level 3
=
2S+deltaT
>
10.
NOTE!
S has to be > 2.5 and deltaT has to be > 3.
Clean area, is the most sensitive condition, requiring a very
clean and stable environment, i.e. the values for all the other
types of areas (level 1, 2 and 3) must not be exceeded.
15.5.1.1
Smoke
– Steam area, level 1
36h
36h
36h
36h
36h
36h
36h
36h
36h
36h
36h
36h
36h
36h
36h
36h
36h
36h
36h
36h
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
A
learning period
contains twenty
36h-periods
(i.e. 20 x 36h = 720h
= 30 days = one month).
During each
36h
-
period
it is recorded if
level 1
is exceeded at least
one time. If so, the
36h
-
period
will get a check-mark, see
example
.
When three (or more) of the
36h
-
periods
during the
learning period
have a check-mark, the Smoke - Steam area Alarm algorithm will be
adapted (i.e. as earliest after 3 x 36h = 108h = 4½ days). In the
example
this will happen in the
36h-period
no. 10 (i.e. after 10 x 36h
= 360h = 15 days).
After the
36h period
no. 20, a new
learning period
starts. The
check-marks are inherited from the previous
learning period
.
Depending on if
level 1
is exceeded or not during each
36h period
,
the check-marks will remain or be removed.
127
Via EBLWin is set if an Area Alarm algorithm shall be automatically
adapted via the Learning function or manually set via EBLWin. If manually
set, also an alternative Area Alarm algorithm can be set that can be controlled
via a time channel.