EBL128 Planning Instructions V2.0.x
126
36h
36h
36h
36h
36h
36h
36h
36h
36h
36h
36h
36h
36h
36h
36h
36h
36h
36h
36h
36h
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
In the
example
, the Smoke - Steam area Alarm algorithm will be
changed back to the Normal area Alarm algorithm after the
36h
period
no. 3, since at that time there are left only two
36h periods
with check-marks in this
learning period
. (If later, one or more
36h
periods
will get a check-mark, the Smoke - Steam area Alarm
algorithm will be adapted again as long as three or more of the
36h
-
periods
during this learning period have a check-mark.)
15.5.1.2
Heater area, level 2
The learning function is the same as for the Smoke - Steam area
Alarm algorithm but
level 2
is used instead of level 1.
15.5.1.3
Cooking
– Welding area, level 3
The learning function is the same as for the Smoke - Steam area
Alarm algorithm but
level 3
is used instead of level 1.
15.5.1.4
Clean area, level 1, 2 & 3
For this area Alarm algorithm to be adapted there must be
no
check-
mark for
level 1
,
level 2
and
level 3
respectively during the
learning
period
, i.e. no check-mark what so ever. The Clean area Alarm
algorithm cannot be adapted until earliest one month after c.i.e. power
on.
The
Clean area Alarm algorithm
will be changed back to the
Normal area Alarm algorithm directly if any
36h period
for
level 1
,
level 2
and
level 3
respectively gets a check-mark, i.e. any check-mark
what so ever.
15.5.1.5
Learning function summary
A detector can adapt the following
area Alarm algorithms
depending
on if and when
level 1
,
level 2
and
level 3
is exceeded or not.
The following is valid for the different type of detectors:
4452
: This detector does
not
use the Learning function.
4400
: This detector uses the Learning function (in Advanced mode),
i.e. the area Alarm algorithms
Normal
,
Smoke – Steam
,
Clean
,
Heater
and
Cooking - Welding
can be adapted.
4401
: This detector uses the Learning function (in Advanced mode),
i.e. the area Alarm algorithms
Normal
,
Smoke – Steam
and
Clean
can be adapted.
15.6
Analog data output
The smoke obscuration value (%/m) and the temperature (°C) can be
shown via the c.i.e. A new value is calculated every second. (The
smoke obscuration value is an average value for the last four seconds.)
The following is valid for the different type of detectors: