EBL128 Planning Instructions V2.0.x
132
17
System properties (settings)
Figure 25. The EBLWin "System properties" dialog box, Page 1 and Page 2.
NOTE!
Default settings in EBLWin might vary depending on
convention.
17.1
System properties dialog box
Opens via the "System" pop-up menu or via menu "System"
(Properties...).
17.1.1
Name
Normally the installation name. (Max. 22 characters.)
17.1.2
User definable text
For user definable text. One row, in total 40 characters. The text will
be shown in the control unit display in quiescent condition. See also
EBL128 Operating Instructions MEW01623.
17.1.3
System properties, Page 1
17.1.3.1
Alert Annunciation
See also chapter "Alert Annunciation", page 105.
Acknowledgement time
: 30
sec.
30 is default. 0-120 (= 2 min.) is possible.
Investigation time
: 3
min.
3 is default. 0-9 is possible.
NOTE!
According to EN54-2, the total delay of fire alarm routing
equipment (Acknowledge time + Investigation time) must not exceed
10 minutes.
Number of zones
: 1
1 is default. 1-4 is possible.
Multiple alarms allowed within same zone
Normally only one Alert Annunciation alarm is allowed within the
zone. If more Alert Annunciation alarms within the zone are
allowed, this checkbox shall be marked.