Panasonic Eco Solutions Nordic AB
MEW01622
Rev: -
EBL128 Planning Instructions V2.0.x
21
S0
: max. 500 mA (Fuse F8).
S1
: max. 200 mA (Fuse F6).
See also chapter "Programmable outputs", page 70.
4.3
Programmable relay output (R0)
Connections to "J1:17-19" according to drawing 128-23.
The output has to be programmed (via EBLWin) regarding:
Type (Control, Fire ventilation, Alarm device, etc.)
Output signal period (steady, intermittent, pulse, delay, etc.)
Logic, i.e. normally open (NO)
or
normally closed (NC).
11
12
Control expression (containing one or more trigger conditions).
NOTE!
The output R0 is as default programmed as output for Fire
alarm routing equipment (Fire brigade tx).
13
Activated output is
indicated by the LED "Fire brigade tx".
14
This output can be disabled
via "door open" or via menu H2/B10. This output can be tested via
menu H1, see the EBL128 Operating Instructions.
See also chapter "Programmable outputs", page 70.
4.4
Relay output for routing equipment (fault
tx) (R1)
Connections to "J1:20-22" according to drawing 128-23.
Not programmable relay output.
12
This output for fault routing
equipment (Fault tx) is activated during normal operation and will be
de-activated when a fault is generated in EBL128
15
. De-activated
output is also indicated by the LED "Fault tx activated". This output
can be disabled via "door open" or via menu H2/B10. This output can
be tested via menu H1, see the EBL128 Operating Instructions.
4.5
Programmable input (I0)
Connections to "J1:9-10" according to drawing 128-22.
The input has to be programmed (via EBLWin) regarding:
Type ("trigger condition")
Supervised / Not supervised
11
In this case: Relay normally not activated / Relay normally activated.
12
Relay contact ratings (COM / NO / NC): max. 2 A @ 30 V DC.
13
A control expression is also required, i.e. Fire Brigade Tx.
Regarding "Fire brigade tx", see also chapters "Alert Annunciation", page 92
and "Fire alarm type A and Fire alarm type B", page 97.
14
It is possible to use a programmable input with trigger condition Activated
routing equipment, to turn on the LED instead.
15
Also if EBL128 becomes powerless (dead) and for "Watch-dog fault".