Panasonic Eco Solutions Nordic AB
MEW01622
Rev: -
EBL128 Planning Instructions V2.0.x
138
There is a button to open a list of:
- fire alarms (selected or all can be reset)
- faults (selected or all can be acknowledged)
- disablements (selected or all can be re-enabled)
- activated interlocking combinations
- service signals (selected or all can be acknowledged)
- open doors
- technical warnings
You can print and save what you see in the list respectively. A filter
function is available.
18.2.3
Selected loop
To the right of the tree view, the tab "Selected loop" is available by
default.
COM loop units can be added two ways. Via the tree view (COM
loop pop-up menu) or via the "Selected loop" tab. Click a COM loop
unit symbol to add the unit to the list. Then edit its properties. The
"Selected loop" list and the tree view will show the same information.
18.2.4
Alarm points
To the right of the of the tree view can the "Alarm points" tab be
available.
This is a list, for the whole system, showing all alarm points and their
properties.
The list can be sorted by clicking the column header respectively.
Double click an alarm point row to open its dialog box.
You can print and save what you see in the list. A filter function is
available.
18.2.5
Interlocking combinations
To the right of the tree view can the "Interlocking combinations" tab
be available.