
Panasonic Eco Solutions Nordic AB
MEW01622
Rev: -
EBL128 Planning Instructions V2.0.x
35
4313
Analog Base with isolator. An analog detector (Sensor) is to be
plugged in 4313. Terminals for ext. LED 2217 / 2218.
Prepared for mechanical lock of the detector. Recess for label
holder 3391. It has also a built-in short circuit isolator. The
function
is described at page 49. The isolator's technical
address is set with Address setting tool 3314 / 4414. The base
has an address label on which both the plugged-in detector's
technical address and the isolator's technical address are to be
written.
The Address setting tool is also used for mode setting:
NORMAL mode
: Used for 4313 in EBL128.
2330 mode
: Not used in EBL128.
2312 mode
: Not used in EBL128.
6.1.1.2
Addressable Manual Call Points
3333
Addressable Manual Call Point.
34
Replaced with 4433, see
below. Conforms to EN54-11. A built-in LED will indicate
that fire alarm is generated, i.e. the glass is broken. Routine
testing can be performed with a supplied test key without
breaking the glass. A hinged polycarbonate flap is protecting
the glass. The technical address is set with Address setting tool
3314 / 4414. The call point has an address label on which the
programmed technical address is to be written.
3333 is to be surface mounted in the supplied red backbox or
flush mounted in a Swedish 65mm circular mounting box. For
indoor use and in dry premises.
The Address setting tool is also used for mode setting.
NORMAL mode
: Flashing or not flashing LED (see Product
leaflet MEW00097) is set via EBLWin.
2330 mode
: Not used in EBL128.
2312 mode
: Not used in EBL128.
4433
Addressable Manual Call Point with isolator. Replaces 3333,
see above. 4433 is like the 3333 unit but it also has a built-in
short circuit isolator. (The function is described at page 49.)
The isolator does
not
use any COM loop address.
The Address setting tool is also used for mode setting.
NORMAL mode
: The built-in short circuit isolator is
in use
.
Flashing or non-flashing LED is set via EBLWin.
2330 mode
: The built-in short circuit isolator is
not in use
.
4433 replaces a
3333
mcp. Flashing or non-flashing LED is set
via EBLWin.
2312 mode
: The built-in short circuit isolator is
not in use
.
4433 replaces a
2333
mcp. Flashing LED.
3339
Enclosed Addressable Manual Call Point.
34
Replaced with
4439, see below. Like the 3333 unit (see above) but another
34
In all conventions the manual call points have a response time < 5 s.