Panasonic Eco Solutions Nordic AB
MEW01622
Rev: -
EBL128 Planning Instructions V2.0.x
27
5.2.2.5
Open circuit state
Open circuit current limit
24
is passed, indicating no or too low zone
line current consumption, i.e. the end-of-line device is not detected,
which generates a fault condition in EBL128. From this state any
other state can be reached / activated.
5.2.2.6
Disconnected state
Via menu H8/S2 (Disconnect / Re-connect zone line) the zone line
input can be disconnected
25
, i.e. there is no voltage on the zone line.
From this state no other state can be reached / activated.
5.3
8 relays expansion board 4581
Up to four 4581 boards can be used.
Each board has to be programmed
via EBLWin regarding:
Address (set via the jumpers "JP2-JP4", see Figure 5, page 25.
The 4581 board has eight programmable relay outputs (Output 0-7).
Connections to "J1:1-16" and "J2" according to drawing 128-31.
Each output has to be programmed
via EBLWin regarding:
Type, i.e. output for Control, Alarm devices, etc.
Output signal period (steady, pulse, delay, etc.)
Logic, i.e. normally open (NO)
or
normally closed (NC)
contacts
26
Control expression (one or more trigger conditions)
For more information, see chapter "Programmable outputs", page 70.
The terminals support a wire size up to 1.13 mm
2
(1.2 mm).
5.4
Inputs and outputs expansion board 4583
Since the max. current consumption for this type of board can be up to
400 mA, only two 4583 board can be used.
Each board has to be programmed
via EBLWin regarding:
Address (set via the jumpers "JP2-JP4", see Figure 5, page 25.
The I/O expansion board 4583 has two programmable supervised or
not supervised voltage outputs (Output 0-1), one programmable
special output (Output 2) for German extinguishing system and five
programmable supervised or not supervised inputs (Input 0-4).
Connections to "J1:1-16" and "J2" according to drawing 128-03 sheet
2/2.
Output 0-1 has to be programmed
via EBLWin regarding:
25
This indicated in EBL128 by the LED "Disablements".
26
Relay contact ratings: Max. 2A @ 30 V DC.