The following table is a
help
when calculating the cable length and/or
the number of units. The table is based on the current consumption at
the lowest power supply voltage allowed i.e. 21 V DC by battery
back-up (no mains).
Recommended cable type is LIHCH-TP 2 x 2 x 0.75 mm
2
.
Wire resistance for this cable is approx. 25 ohm / 1000 m.
Up to four units can be connected but it is depending on the type of
units and the cable (type and length).
Number
of units
Allowed cable resistance (ohm) / length (m)
Units
1735, 1736
Units
1728, 1735, 1736,
1826, 1828 &
no printers 1835
Units
1728, 1735, 1736,
1826, 1828 &
one
154
printer 1835
4
25 / 500
21 / 420
4 / 80
3
34 / 680
28 / 560
10 / 200
2
50 / 1000
42 / 840
16 / 320
1
100 / max. 1200
84 / max. 1200
18 / 360
Explanation: 25 (ohm) ÷ 25 (ohm wire resistance per 1000 m) = 1000
m but the wire goes from the c.i.e. to the last unit and back to the c.i.e.
again, i.e. the cable length = 1000 (m) ÷ 2 = 500 m.
NOTE!
The table is based on the recommended cable type. If a cable with
greater area is used the wire resistance (ohm per 1000 m) will be
lower and the possible cable length will be longer.
It is also possible to use an external power supply, e.g. 3366, when a
greater number of units are required or if a longer cable length is
required.