Panasonic Eco Solutions Nordic AB
MEW01622
Rev: -
EBL128 Planning Instructions V2.0.x
158
Maximum conductor resistance
5
10
15
20
25
30
35
40
45
0
40
80
120
160
200
240
280
320
Total COM loop unit current consumption
C
o
n
d
u
c
to
r
re
s
is
ta
n
c
e
Ohm
mA
Figure 30. Graphs showing the total conductor resistance in relation to the
COM loop units' total current consumption.
NOTE!
The graphs start at "0
mA" but graph 1 ends at "320 mA" and graph 2 ends at "350 mA". End of
graph = max. allowed loop current.
NOTE!
The total conductor resistance (ohm) = L conductor (ohm) +
C conductor (ohm).