o
A socket for an
optional
Communication module (RS485
transceiver component) 4552, which will provide an RS485
interface (serial line) for up to eight Display Units (1735 /
1736 and/or 1826 / 1828 and/or 1728). Max. one 1826 with
printer. Connections and more information, see drawing 128-
23.
On the RS485 serial line can as an alternative, up to eight
German Fire Brigade Control Panels (Feuerwehr-Bedienfeld)
FBF 2003
3
and/or German Fire Brigade Indicator Panels
(Feuerwehr-Anzeigetableau)
FAT 2002
3
be connected.
o
RS232 interface ("D" connector) for a PC with EBLWin.
Connections and more information, see drawing 128-25.
o
RS232 interface for a Web-server 1598. Connections and more
information, see drawing 128-25.
o
24 V DC power supply output for a Web-server 1598.
Connections and more information, see drawing 128-25.
Built-in power supply (rectifier) and space for back-up batteries.
Connections and more information, see drawing 128-24.
Space for
optional
expansion board holder (Expansion boards
mounting kit 4551). Up to four expansion boards can be
mounted in the holder.
Space for routing equipment.
DIN-rail (and space) for a Web-server 1598.
Cable inlets (rubber grommet / knock-outs) on the top, bottom and
back sides.
The door has a Plexiglas ahead of the front, see Figure 1. A key is
required to open the door to get full access to the push buttons on the
front, i.e. the
F
ire
B
rigade
P
anel (
FBP
) and the
C
ontrol
P
anel (
CP
).
Figure 2. The EBL128 front. The look might vary depending on
the country (language), configuration, etc. (e.g. English texts as
in the figure). LEDs & push buttons are described in the
EBL128 Operating Instructions.
3
Manufacturer: IFAM GmbH, Erfurt, Germany. www.ifam-erfurt.de
FBP