EBL128 Planning Instructions V2.0.x
39
programmed technical address is to be written.
The Address setting tool is also used for mode setting:
NORMAL mode
: 4300 in this mode is in EBLWin, for the
smoke detector, set to one of six alarm algorithms H-15, H-35,
L-15, L-35,
N-15
or N-35 and for the heat detector set to one of
three alarm algorithms for class
A1
(static response temp. 54-
65°C), A2 S (54-70°C) or B S (69-85°C).
2330 mode
: 4300 in this mode (+ base 3312) works like the
ionization smoke detectors 2316 / 2317 (+ base 2330).
2312 mode
: Not used in EBL128.
4400
Analog multi detector. Replaces 4300, see above. 4400 is a
smoke detector and a heat detector in one housing. Scattered
light (i.e. reflection of infrared light) is used to detect
smoke
and the
heat
sensing element is a thermistor. The detector has
unleaded soldering.
Shall be plugged in an analog base 3312xx/3379/4313. Built-in
LEDs (red) are blinking to indicate that the detector
40
has
activated a fire alarm. Prepared for mechanical lock (screw
attached) – if required. 4400 has a little different design than
the 4300 detector and the smoke chamber net has even smaller
holes that will keep insects and particles
41
larger than smoke
particles out of the chamber.
The COM loop address (Technical address) is set with the
Address setting tool 3314 /
4414
. The detector has an address
label on which the programmed technical address can be
written.
The Address setting tool is also used for
mode setting
:
Advanced mode
: 4400 has to be set to Advanced mode via the
Address setting tool
4414
.
Note, the Address setting tool 3314
cannot be used to set Advanced mode!
In Advanced mode this
detector will use algorithms in the detector for fire alarm
evaluation. It can be set to a Learning function
or
via EBLWin
to one of five area alarm algorithms (Normal, Clean,
Smoke/Steam, Cooking/Welding or Heater area), see chapter
"Advanced mode", page 123. An alternative area alarm
algorithm can be used via a time channel. 4400 has a green
polling LED. Via EBLWin is set if the green polling LED shall
blink when the detector is polled or never blink. Note, the LED
will not be blinking if the detector is in Test mode.
In Advanced mode only one COM loop address will be
occupied for the multi detector.
NORMAL mode
: 4400 in this mode has to be programmed in
EBLWin as a
4300
detector, i.e. the 4400 detector will work as
and replace the Analog multi detector 4300 (see 4300 above)
and two COM loop addresses will be occupied, see 4300 above.
40
I.e. the heat detector and/or the smoke detektor.
41
For example dust, steam, etc.