AFX SERIES® OPERATION MANUAL
SECTION 8: REMOTE PROGRAMMING
Entire Contents Copyright
2016 by Pacific Power Source, Inc. (PPS) • All Rights Reserved • No reproduction without written authorization from PPS.
AFX Series Power Source Operation Manual
Page 213 of 274
8.9.9
System Remote Access Commands
Command Syntax
SYSTem:REMote:INHibit
Description
This command enables the remote control inhibit protection
mechanism of the power source. This mode may be used to protect
against inadvertent remote operation over LAN or similar connections
that may endanger a local operator working with the power source.
Parameters
< 0 | OFF | 1 | ON >
Parameter Format
<b>
Example
SYST:REM:INH ON
Query Format
SYSTem:REMote:INHibit?
Returned Data Format
<b>
Query Example
SYST:REM:INH?
1
Command Syntax
SYSTem:REMote:ENAble
Description
This command enables or disables remote control of the power source.
Parameters
< 0 | OFF | 1 | ON >
Parameter Format
<b>
Example
SYST:REM:ENA ON
Query Format
SYSTem:REMote:ENAble?
Returned Data Format
<b>
Query Example
SYST:REM:ENA?
1
Command Syntax
SYSTem:REMote:PASSword
Description
This command sets the remote control password required to enable
remote operation.
Parameters
Four digit number
Parameter Format
<nr1>
Example
SYST:REM:PASS 1234
Query Format
SYSTem:REMote:PASSword?
Returned Data Format
<nr1>
Query Example
SYST:REM:PASS?
1234
Command Syntax
SYSTem:REMote:ACCESS:GLOBal
Description
This command enables or disables global remote control access. Global
access enables all operation of the power source to be remote
controlled.
Parameters
<0 | DISABLED | 1 | ENABLED>
Parameter Format
<b>
Example
SYST:REM:ACCESS:GLOB 0
Query Format
SYSTem:REMote:ACCESS:GLOBal?
Returned Data Format
<b>
Query Example
SYST:REM:ACCESS:GLOB?
0
Summary of Contents for 3120AFX
Page 273: ......