Command Syntax
[SOURce:]VPEAK:MARGin
Description
This command sets the over voltage protection trip level as an absolute
value. Thus, if the output voltage exceeds the programmed v
the Vpeak Margin, the OVP protection will trip off the output and
generate an OVP fault.
For example., if 230Vrms is programmed in AC mode and the Vpeak
margin is set to 20, the OVP will trip at 230 *
2 + 20 =345Vpeak.
Parameters
0.0 – 500.0
Parameter Format
<nr2>
Example
VPEAK:MARG 20.0
Query Format
[SOURce:]VPEAK:MARGin?
Returned Data Format
<nr2>
Query Example
VPEAK:MARG?
20.0000
8.7.3
Frequency Programming Commands
Command Syntax
[SOURce:]FREQuency
Description
Sets output frequency for all phases. Not valid when the source is in DC
mode. Sending a FREQ command while the source is in DC mode will
result in an error. The query form will return 0.000 when in DC mode.
Parameters
15.00 – 1200.0
Parameter Format
<nr2>
Example
FREQ 400.0
Query Format
[SOURce:]FREQuency?
Returned Data Format
<nr2>
Query Example
FREQ?
400.0000
Command Syntax
[SOURce:]FREQuency:SLEW
Description
Sets the frequency slew rate in Hz/msec. This command is not valid
when in DC mode.
Parameters
0.01 – 1200.00
Parameter Format
<nr2>
Example
FREQ:SLEW 100.0
Query Format
[SOURce:]FREQuency:SLEW?
Returned Data Format
<nr2>
Query Example
FREQ:SLEW?
100.0000