Appendix E
PDU Connections
256
Pillar Data Systems Confidential
Current and Power Summary
The following tables provide the current and power used by
different numbers of Bricks. The calculations include the
current and power used by
one
Slammer.
Table 101 Current and power in a 115 V system
Bricks
Current (amps)
Watts
2
13.334
1386.6
3
16.001
1644.9
4
18.668
1903.2
5
21.335
2161.5
6
24.002
2419.8
7
26.669
2678.1
8
29.336
2936.4
9
32.003
3194.7
10
34.670
3453.0
11
37.337
3711.3
12
40.004
3969.3
13
42.671
4227.9
14
45.338
4486.2