Chapter 4
Replace Slammer Chassis
109
Pillar Data Systems Confidential
• The network interface module for each CU.
• The private interconnect module for each CU.
4 Connect all cables to the Slammer:
• Storage System Fabric (SSF) cables that connect to
the Bricks. Gently insert the cables straight into the
socket and use gentle pressure to latch them in
place.
Important!
Do not rock the connector from side to
side or up and down to insert it.
• SSF cables that cross-connect the Slammer.
• Private management network cables that connect to
the Pilot.
• Public Ethernet cables, which are connected to the
network ports in the network interface module.
• Power cables.
Note: Refer to the one-Slammer or two-Slammer cabling
tables in the Appendix. Use the set of tables that is
appropriate for your Axiom system.
5 For the power distribution units (PDUs) that will supply
power to the Slammers, flip the PDU circuit breaker(s) to
their on positions. Be sure to turn on power to both CUs
of all Slammers.
6 In the Guided Maintenance screen, click the Next button.