Chapter 5
Replace Brick Power Supply / Fan Modules
134
Pillar Data Systems Confidential
5 Unscrew the two screws that secure the locking tabs to
the power supply module casing. Springs retain the
screws in the locking tabs.
6 Push the power supply module’s two locking tabs down,
which disengages the power supply module from the
Brick midplane.
7 Slide the power supply / fan module out of the chassis
and set it aside.
CAUTION
Immediately replace the component to maintain
proper airflow and cooling. Over-temperature conditions will
occur if the replacement FRU is not installed into the chassis.
Over-temperature conditions can damage other components.
Important!
Because of airflow impacts within the Brick, swap
a power supply / fan module as quickly as possible.
Insert a Brick Power Supply / Fan Module
After you insert this FRU into a Brick control unit (CU), use
Guided Maintenance to complete the replacement procedure.
Important!
If Guided Maintenance encounters a problem at
this stage, you must contact Technical Support to continue
Guided Maintenance for this FRU.
When the FRU replacement process is complete, the Axiom
system reports the status of the FRU.
!