Appendix E
PDU Connections
254
Pillar Data Systems Confidential
Cabling 208 V Three-Phase PDUs
Axiom systems that have a pair of 208 V / 30 A three-phase
PDUs can support:
• The Pilot
• One Slammer
• 13 Bricks
• A Data Management Systems (DMS) unit.
Note: Alternatively, you can replace the DMS unit with an
additional Brick in phase A.
shows the power cable configuration for a two-
PDU, 208 V / 30 A, three-phase system.
Important!
For fewer than 13 Bricks, be sure to balance the
load across the three phases.
To add a second Slammer, replace two Bricks that are
plugged into phase A or phase C.