The table below lists the Error messages related to the System on which the DTM is installed.
52
CX-Server could not be config-
ured
Configuration of CX-Server failed.
•
Make sure the settings within the
Device Set-up tab are correct.
Select the Test Button to check
this.
•
Make sure the Personal Com-
puter COM port selected within
the Device Set-up Configuration
is not in use by another applica-
tion. If it is close the connection
from within the other application.
•
Restart CX-PROFIBUS.
•
Restart Personal Computer to
ensure COM port is released.
•
Ensure the correct version of CX-
Server is installed on the Per-
sonal Computer. Refer to the
Master Manual for installation
details.
•
When the problem has been
removed, perform one of the fol-
lowing successfully to confirm
the problem has been solved:
* Select the Configure Button in
the Device Set-up tab
* Select the Test Button in the
Device Set-up tab
53
CX-Server could not be initialized Initialization of CX-Server was not
possible.
•
Ensure the correct version of CX-
Server is installed on the Per-
sonal Computer. Refer to the
Master Manual for installation
details.
54
DTM cannot configure the con-
nected unit. DTM needs to be
upgraded
This may be caused by required
function which are not supported by
the DTM.
Make sure the correct version of the
DTM is being used. If it is not then
install the correct version and reat-
tempt download.
Number
Message
Description
Correction
100
Connected device can not be con-
figured with this DTM
Incorrect firmware type.
Make sure the unit connected is a
CJ1W-PRM21 or CS1W-PRM21.
Make sure the Unit number in the
Device set-up corresponds to the
physical unit.
101
Incorrect version of CX-Server.
Incorrect version of CX-Server.
Make sure the correct CX-Server
version is installed. Version must be
1.7 and up.
102
[Name of the function] called with
improper parameters
Container called a function with
NULL pointer.
There must be problem in the con-
tainer. Reinstall CX-PROFIBUS, if
problem persists contact supplier.
103
Received XML Document does
not fit it's XML schema
Container called a function with an
improper XML document.
There must be a problem in con-
tainer program. Reinstall CX-PROFI-
BUS, if problem persists contact
supplier.
Number
Message
Description
Correction
Summary of Contents for SYSMAC CJ1W-PRM21
Page 2: ...iv...
Page 36: ...22 Basic Operating Procedure Section 1 5...
Page 52: ...38 Defining PROFIBUS DP in the Software Section 2 5...
Page 112: ...98 Allocated CIO Area Words Section 4 2...
Page 122: ...108 Command Response Reference Section 5 2...
Page 160: ...146 Replacing the Unit Section 7 8...
Page 174: ...160 Appendix...
Page 180: ...166 I O Data Conversions Appendix D...
Page 186: ...172 Configurator Error and Warning Messages Appendix E...
Page 187: ...173 Index...
Page 188: ...174 Index...
Page 190: ...176 Revision History...