The following end codes can be returned by the Unit in response to the RUN
command:
5-2-3
STOP (0402)
Initiates a state changes within the PROFIBUS-DP Master Unit. This com-
mand will disable a pre-allocated slave station in the PROFIBUS-DP Master
Unit. The targeted slave station will temporarily be removed from the Unit’s list
of active stations. The Unit will Unlock the slave station and stop communica-
tion with it.
Note The configured slave stations are by default enabled. A disabled slave station
can be enabled using the RUN command (see
The targeted slave station is defined by the station code in the command.
Command Format
Response Format
Parameters
Station code (command)
Defines the slave station to be enabled state as follows:
High byte:
Always set to 81(Hex).
Low byte:
00 ~ 7D (Hex): Defines the slave station network address.
Response Codes
The following end codes can be returned by the Unit in response to the STOP
command:
Response code
Description
0000
Normal.
0203
Slave station not allocated to the PROFIBUS-DP Master.
0402
Service not supported by Unit model / version.
1001
Command too large.
1002
Command too short.
110C
• Mode code setting not supported (code exceeds 01).
• Invalid station code (High byte not equal to 81)
• Invalid target slave address (exceeds 125).
2605
Slave station is already enabled.
02
04
Station
code
Command
code
02
04
End code
Command
code
Response code
Description
0000
Normal.
0203
Slave station not allocated to the PROFIBUS-DP Master.
0402
Service not supported by Unit model / version.
Summary of Contents for SYSMAC CJ1W-PRM21
Page 2: ...iv...
Page 36: ...22 Basic Operating Procedure Section 1 5...
Page 52: ...38 Defining PROFIBUS DP in the Software Section 2 5...
Page 112: ...98 Allocated CIO Area Words Section 4 2...
Page 122: ...108 Command Response Reference Section 5 2...
Page 160: ...146 Replacing the Unit Section 7 8...
Page 174: ...160 Appendix...
Page 180: ...166 I O Data Conversions Appendix D...
Page 186: ...172 Configurator Error and Warning Messages Appendix E...
Page 187: ...173 Index...
Page 188: ...174 Index...
Page 190: ...176 Revision History...