12
PROFIBUS-DP Master Unit
Section 1-3
Protocol Specification
FI
NS m
e
s
s
agi
ng
Reading Slave station diagnostics
The MEMORY AREA READ (0101) FINS command can be used to
obtain the last received Slave Diagnostics message.
Reading and controlling the error log
The internal error log records the history of error events. The Unit
supports the following Error Log related FINS commands:
• ERROR LOG READ
• ERROR LOG CLEAR
Station state changes
Allocated Slave stations can be disabled and enabled in order to
temporarily remove them from data exchange services. The internal
error log records the history of error events. The Unit supports the
following FINS commands to implement this:
• RUN
• STOP
E
rro
r lo
g
Error history size and storage
The PROFIBUS Master unit supports storage of up to 80 error
events, including time stamps in volatile memory.
16 error events can be logged in non-volatile memory
Item
Specification
Item
Specification
P
R
O
F
IB
U
S
i
n
te
rf
a
c
e
Applicable standards
EN50170, Volume 2
Protocol type supported
PROFIBUS-DP
PROFIBUS Unit types
PROFIBUS-DP Class 1 Master
PROFIBUS Media type
RS-485, galvanically isolated from the PLC
PROFIBUS Connector
9-pin sub-D female connector (#4/40 UNC thread)
Termination to be provided by the cable connector according to
EN50170
Unit station address range
0
~ 125, set through Configurator
Number of slave stations supported
125 max, address range
0
~ 125
baud rates supported
Selectable through Configurator:
• 9.6 kbit/s
• 19.2 kbit/s
• 45.45 kbit/s
• 93.75 kbit/s
• 187 kbit/s
• 500 kbit/s
• 1.5 Mbit/s
• 3 Mbit/s
• 6 Mbit/s
• 12 Mbit/s
Bus timing definitions
Calculated by Configurator
PROFI
B
US-
D
P Ser
v
ic
e
s
Master Class 1 - Slave cyclic services
• Set_Prm
• Chk_Cfg
• Data_Exchange
• Slave_Diag
• Global_Control - CLEAR
Master Class 1 - Slave acyclic services
Not supported
Master Class 1 - Slave services
available to the PLC
Global_Control, initiated from CIO Word:
Can be addressed to all slave stations or a specified group of
slaves stations
Supported commands:
• SYNC
• UNSYNC
• FREEZE
• UNFREEZE
Master - Master services
Not supported
Summary of Contents for SYSMAC CJ1W-PRM21
Page 2: ...iv...
Page 36: ...22 Basic Operating Procedure Section 1 5...
Page 52: ...38 Defining PROFIBUS DP in the Software Section 2 5...
Page 112: ...98 Allocated CIO Area Words Section 4 2...
Page 122: ...108 Command Response Reference Section 5 2...
Page 160: ...146 Replacing the Unit Section 7 8...
Page 174: ...160 Appendix...
Page 180: ...166 I O Data Conversions Appendix D...
Page 186: ...172 Configurator Error and Warning Messages Appendix E...
Page 187: ...173 Index...
Page 188: ...174 Index...
Page 190: ...176 Revision History...