Troubleshooting Using LED Indicators
Section 7-2
Note The table above assumes that the RUN and the PRM LED indicators are ON
and the ERH indicator is OFF. Otherwise, refer to section
, section
Flashing/
Lit
Not lit
Not lit
Not a valid combination.
Lit
A Bus disturbance error has been detected.
This indicates a termination error (termina-
tion resistors are missing, or inductors are
not used), or two slave devices with the
same address.
• Switch the Unit to OFFLINE mode.
• Terminate the network at the appropriate
places (see section
• Check if any other faulty devices are on
the same network.
• Switch the Unit to CLEAR / OPERATE
mode again.
Flashing
• None of the allocated slave stations
responds to the Master’s request mes-
sages.
• None of the slaves is in Data_Exchange
with the Master Unit.
This may indicate a loose network connec-
tor on the Master, or a broken cable.
• Switch the Unit to OFFLINE mode.
• Check the network wiring.
• Check if any other faulty devices are on
the same network.
• Check if actual slave addresses match
the configured addresses.
• Check if the slave parameter settings are
correct. If necessary change them, and
download them again.
• Switch the Unit to CLEAR / OPERATE
mode again.
Lit
Not-Lit
There are no errors. The Unit is in CLEAR or OPERATE mode and exchanging data.
Lit
Not a valid combination.
Flashing
At least one slave station has responded to
the Master’s request messages and is not
in Data Exchange. There is also at least
one slave which has either
• not responded to the Master’s requests
messages, or
• been parameterized incorrectly.
• Switch the Unit to OFFLINE mode.
• Check the network wiring.
• Check if any other faulty devices are on
the same network.
• Check if the slave parameter settings are
correct. Re-download after correction.
• Switch the Unit to CLEAR / OPERATE
mode again.
BST
COMM
BF
Probable cause
Correction
Summary of Contents for SYSMAC CJ1W-PRM21
Page 2: ...iv...
Page 36: ...22 Basic Operating Procedure Section 1 5...
Page 52: ...38 Defining PROFIBUS DP in the Software Section 2 5...
Page 112: ...98 Allocated CIO Area Words Section 4 2...
Page 122: ...108 Command Response Reference Section 5 2...
Page 160: ...146 Replacing the Unit Section 7 8...
Page 174: ...160 Appendix...
Page 180: ...166 I O Data Conversions Appendix D...
Page 186: ...172 Configurator Error and Warning Messages Appendix E...
Page 187: ...173 Index...
Page 188: ...174 Index...
Page 190: ...176 Revision History...