81
Generic Slave Device DTM
Section 3-4
retrieving it from the PROFIBUS-DP Master Unit. A Green LED indicator in
the lower left corner will indicate whether or not the device is on-line.
Diagnostics Tab
The Diagnostics tab displays basic diagnostics for the slave. An example of
the Diagnostic tab is shown below. The diagnostics information is displayed
as red and green LED indicators. Red LED indicators refer to error events.
Green LED indicator refer to status situations.
The LED indicators are listed in the table below.
Name
Description
Master lock
The slave station has been parameterized by another master.
Parameter fault
The last received parameter data from the Master Unit have been rejected. The parameter
data in the slave station differ from the parameter sent by the Master Unit.
Invalid slave response
The slave has returned an invalid response to a Master request message.
Function Not supported
The Master Unit has sent a message to the slave station, which is not supported by the sta-
tion.
Extended diagnostics
The diagnostics message returned by the slave station contains extended diagnostics, i.e. it
contains more than the mandatory 6 bytes.
Configuration fault
The last received configuration data from the Master Unit have been rejected. The configura-
tion data in the slave station differ from the configuration sent by the Master Unit.
Station not ready
The slave station is not yet ready for data transfer (the parameters data and the configuration
data have been accepted).
Station not existent
The slave does not respond to any of the request messages sent by the master. If set the
diagnostic bits contains the state of the last diagnostic message or the initial value.
Slave deactivated
When set is indicates that the slave station has been disabled (i.e. using the STOP FINS
command). The slave station is allocated to the Master Unit, but removed from cyclic pro-
cessing.
Sync mode
When set to ON, the slave station has been set to the Sync mode, using the global com-
mand.
Freeze mode
When set to ON, the slave station has been set to the Freeze mode, using the global com-
mand.
Watchdog on
The watchdog has been enabled at the slave station (through the appropriate setting in the
parameterization message).
Slave device
Indicates that the device is a slave station.
Summary of Contents for SYSMAC CJ1W-PRM21
Page 2: ...iv...
Page 36: ...22 Basic Operating Procedure Section 1 5...
Page 52: ...38 Defining PROFIBUS DP in the Software Section 2 5...
Page 112: ...98 Allocated CIO Area Words Section 4 2...
Page 122: ...108 Command Response Reference Section 5 2...
Page 160: ...146 Replacing the Unit Section 7 8...
Page 174: ...160 Appendix...
Page 180: ...166 I O Data Conversions Appendix D...
Page 186: ...172 Configurator Error and Warning Messages Appendix E...
Page 187: ...173 Index...
Page 188: ...174 Index...
Page 190: ...176 Revision History...