92
Allocated CIO Area Words
Section 4-2
4-2-4
Master Status 1 (Word n+5)
The Master Status 1 word collects all status information related to the PROFI-
BUS-DP Master function. Any errors related to the PROFIBUS-DP Master
function are collected in the Master status 2 word.
Word n+5 [n = CIO 1,500 + (25 x unit number)]
13
Error log storage
error
ON
Unit
The Error log storage error flag will be turned ON if an error occurred
during an attempt to write the Error log to internal non-volatile memory.
If the error occurred, the Error log data in the non-volatile memory may
be corrupted. Upon a restart the Unit will attempt to repair the Error log.
OFF
Unit
When set to OFF, this bit indicates that the Error log has been trans-
ferred to the non-volatile memory successfully.
14
to
15
Reserved by sys-
tem
---
---
These bits will be set to OFF by the Unit.
Bit
Name
Status
Controlled
by
Unit operation
Word n+5
15 14 13 12 11 10 9
8
7
6
5
4
3
2
1
0
Auto-Clear enabled
Unit contains a valid configuration
Unit in OPERATE mode
Unit in STOP mode
Unit in CLEAR mode
Unit in OFFLINE mode
Unit in Data-Exchange
Bit
Name
Status
Controlled
by
Unit operation
00
Unit in OPERATE
mode
ON
Unit
Indicates that the Unit is in OPERATE mode.
In OPERATE mode the PROFIBUS-DP Master Unit will parameterize
all allocated slave stations, and commence I/O Data-Exchange.
OFF
Unit
Indicates that the Unit is not in OPERATE mode.
01
Unit in STOP mode ON
Unit
Indicates that the Unit is in STOP mode.
In STOP mode, the Unit will be ONLINE, connected to the network, but
not communicate with its slave stations.
OFF
Unit
Indicates that the Unit is not in STOP mode.
02
Unit in CLEAR
mode
ON
Unit
Indicates that the Unit is in CLEAR mode.
In CLEAR mode the PROFIBUS-DP Master Unit will parameterize all
allocated slave stations. If this is accomplished successfully, it will read
all input data of the allocated slave stations, but it will send zeros or
empty output messages to all slave stations.
OFF
Unit
Indicates that the Unit is not in CLEAR mode.
03
Unit in OFF-LINE
mode
ON
Unit
Indicates that the Unit is in OFF-LINE mode.
In the OFF-LlNE mode the Unit will be disconnected from the network.
OFF
Unit
Indicates that the Unit is not in OFF-LINE mode.
Summary of Contents for SYSMAC CJ1W-PRM21
Page 2: ...iv...
Page 36: ...22 Basic Operating Procedure Section 1 5...
Page 52: ...38 Defining PROFIBUS DP in the Software Section 2 5...
Page 112: ...98 Allocated CIO Area Words Section 4 2...
Page 122: ...108 Command Response Reference Section 5 2...
Page 160: ...146 Replacing the Unit Section 7 8...
Page 174: ...160 Appendix...
Page 180: ...166 I O Data Conversions Appendix D...
Page 186: ...172 Configurator Error and Warning Messages Appendix E...
Page 187: ...173 Index...
Page 188: ...174 Index...
Page 190: ...176 Revision History...