97
Allocated CIO Area Words
Section 4-2
4-2-9
Slave New Diagnostics Flags (Word n+17 to Word n+24)
The Slave New Diagnostics flags indicate for each slave station if it sent a
new diagnostics message to the PROFIBUS-DP Master Unit, since the last
time it was read or cleared by the CS/CJ-series PLC. The flags are allocated
to a block of eight CIO words, and each bit in the block corresponds to a sta-
tion address.
Word n+17 to n+24 [n = CIO 1,500 + (25 x unit number)]
15 14 13 12 11 10 9
8
7
6
5
4
3
2
1
0
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
Word n+17
31
30
29
28
27
26
25
24
23
22
21
20
19
18
17
16
Word n+18
47
46
45
44
43
42
41
40
39
38
37
36
35
34
33
32
Word n+19
63
62
61
60
59
58
57
56
55
54
53
52
51
50
49
48
Word n+20
79
78
77
76
75
74
73
72
71
70
69
68
67
66
65
64
Word n+21
95
94
93
92
91
90
89
88
87
86
85
84
83
82
81
80
Word n+22
111 110 109 108 107 106 105 104 103 102 101 100
99
98
97
96
Word n+23
125 124 123 122 121 120 119 118 117 116 115 114 113 112
Word n+24
Slave station 00 ~ 15
Slave station 16 ~ 31
Slave station 32 ~ 47
Slave station 48 ~ 63
Slave station 64 ~ 79
Slave station 80 ~ 95
Slave station 96 ~ 111
Slave station 112 ~ 125
Bit
Name
Status
Controlled
by
Unit operation
–
Slave New Diag-
nostics flags
ON
Unit
If the bit corresponding to a slave station address is ON, it indicates that
this slave station
• is allocated to the PROFIBUS-DP Master Unit, and
• has sent new diagnostics message to the PROFIBUS-DP Master
Unit.
In this case, the PROFIBUS-DP Master Unit must be in CLEAR mode
or OPERATE mode.
OFF
Unit
If the bit corresponding to a slave station address is OFF, it indicates
that
• the slave station has not sent a new diagnostics message to the
PROFIBUS-DP Master Unit, since the last time it was read or cleared,
or
• the slave station has not been allocated to this PROFIBUS-DP Master
Unit, or
• the PROFIBUS-DP Master Unit is not in CLEAR or OPERATE mode
Note
In case an allocated slave station is not responding, and there-
fore not sending a diagnostics message, the PROFIBUS-DP
Master Unit itself will provide a diagnostics message to the PLC
CPU containing the mandatory first 6 bytes. This diagnostics
message will then indicate that the slave is not responding.
Summary of Contents for SYSMAC CJ1W-PRM21
Page 2: ...iv...
Page 36: ...22 Basic Operating Procedure Section 1 5...
Page 52: ...38 Defining PROFIBUS DP in the Software Section 2 5...
Page 112: ...98 Allocated CIO Area Words Section 4 2...
Page 122: ...108 Command Response Reference Section 5 2...
Page 160: ...146 Replacing the Unit Section 7 8...
Page 174: ...160 Appendix...
Page 180: ...166 I O Data Conversions Appendix D...
Page 186: ...172 Configurator Error and Warning Messages Appendix E...
Page 187: ...173 Index...
Page 188: ...174 Index...
Page 190: ...176 Revision History...