15
PROFIBUS-DP Master Unit
Section 1-3
PROFIBUS Connector
9-pin sub-D female connector (#4/40 UNC
thread)
Termination provided through a switch on
the unit according to EN50170
9-pin sub-D female connector (#4/40 UNC
thread)
Termination must be provided by the cable
connector according to EN50170
Unit station address range
0
~ 125, set through Configurator
0
~ 125, set through Configurator
Number of Slave stations
supported on the network
125 max, address range
0
~ 125
125 max, address range
0
~ 125
baud rates supported
Selectable through Configurator:
• 9.6 kbit/s
• 19.2 kbit/s
• 93.75 kbit/s
• 187 kbit/s
• 500 kbit/s
• 1.5 Mbit/s
• 3 Mbit/s
• 6 Mbit/s
• 12 Mbit/s
Selectable through Configurator:
• 9.6 kbit/s
• 19.2 kbit/s
• 45.45 kbit/s
• 93.75 kbit/s
• 187 kbit/s
• 500 kbit/s
• 1.5 Mbit/s
• 3 Mbit/s
• 6 Mbit/s
• 12 Mbit/s
Bus timing definitions
Calculated by Configurator
Calculated by Configurator
Master Class 1 - Slave cyclic
services
• Set_Prm
• Chk_Cfg
• Data_Exchange
• Slave_Diag
• Global_Control - CLEAR
• Set_Prm
• Chk_Cfg
• Data_Exchange
• Slave_Diag
• Global_Control - CLEAR
Master Class 1 - Slave acy-
clic services
• Get_Cfg
• Set_Slave_Addr
• Rd_In
• Rd-Out
Not supported
Master Class 1 - Slave ser-
vices available to the PLC
Global_Control, initiated from CIO Word:
Can be addressed to one or all slave sta-
tions or a specified group of slaves stations
Supported commands:
• SYNC
• UNSYNC
• FREEZE
• UNFREEZE
• CLEAR
Global_Control, initiated from CIO Word:
Can be addressed to all slave stations or a
specified group of slaves stations
Supported commands:
• SYNC
• UNSYNC
• FREEZE
• UNFREEZE
Master - Master services
Not supported
Not supported
Error reporting
Error numbers are transferred to CIO word
Internal logging not supported
80 error events can be logged in volatile
memory.
16 error events can be logged in non-volatile
memory
Errors can be retrieved through FINS mes-
sages
Item
C200HW-PRM21
CS1W-PRM21/CJ1W-PRM21
Summary of Contents for SYSMAC CJ1W-PRM21
Page 2: ...iv...
Page 36: ...22 Basic Operating Procedure Section 1 5...
Page 52: ...38 Defining PROFIBUS DP in the Software Section 2 5...
Page 112: ...98 Allocated CIO Area Words Section 4 2...
Page 122: ...108 Command Response Reference Section 5 2...
Page 160: ...146 Replacing the Unit Section 7 8...
Page 174: ...160 Appendix...
Page 180: ...166 I O Data Conversions Appendix D...
Page 186: ...172 Configurator Error and Warning Messages Appendix E...
Page 187: ...173 Index...
Page 188: ...174 Index...
Page 190: ...176 Revision History...